TRIO-PS-2G/1AC/24DC/10/B+D

105897_en_00

PHOENIX CONTACT

21 / 26

Normal mounting position

Rotated mounting position 90° X-axis

Z

X

Y

I

N

1.5 x I

N

-25

0

10

20

30

40

50

60

70

80

[°C]

[A]

Summary of Contents for TRIO-PS-2G/1AC/24DC/10/B+D

Page 1: ...heavy loads thanks to dynamic boost 1 5 x IN for 5 seconds Simplified error diagnostics for remote signaling via DC OK signal contact OVP Over Voltage Protection limits surge voltages to 30 V DC EN 6...

Page 2: ...the customer 12 6 4 Performing high voltage testing 12 7 Basic circuit diagram 13 8 Structure 13 9 Cooling 14 10 Mounting position and dimensions 14 10 1 Mounting position 14 10 2 Device dimensions 1...

Page 3: ...rating 20 17 1 Temperature dependent derating 20 17 2 Installation height 20 17 3 Position dependent derating 20 18 Operating modes 24 18 1 Series operation 24 18 2 Parallel operation 24 18 3 Redundan...

Page 4: ...ic locking of the set nominal currents For installation on DIN rails CBM E4 24DC 0 5 10A NO R 2905743 1 Multi channel electronic device circuit breaker with active current limitation for protecting ei...

Page 5: ...ues typ 3 1 A 100 V AC 2 4 A 120 V AC 1 4 A 230 V AC 1 4 A 240 V AC 2 5 A 110 V DC 1 1 A 250 V DC Discharge current to PE typ 3 5 mA 0 8 mA 264 V AC 60 Hz Mains buffering 20 ms 120 V AC 20 ms 230 V AC...

Page 6: ...rmanent Control deviation change in load static 10 90 1 Control deviation Dynamic load change 10 90 10 Hz 3 Control deviation change in input voltage 10 0 1 Short circuit proof yes No load proof yes R...

Page 7: ...mm 1 5 mm Stranded conductor cross section with ferrule 0 2 mm 1 5 mm Conductor cross section AWG 24 16 Stripping length 8 mm Reliability 230 V AC MTBF IEC 61709 SN 29500 2200000 h 25 C 1300000 h 40...

Page 8: ...amplitude 25 Hz 100 Hz 4g acceleration Shock 18 ms 30g in each space direction according to IEC 60068 2 27 Degree of pollution 2 Climatic class 3K3 in acc with EN 60721 Overvoltage category EN 60950 1...

Page 9: ...Immunity according to EN 61000 6 1 residential EN 61000 6 2 industrial CE basic standard Minimum normative requirements of EN 61000 6 2 CE immunity for industrial environments Higher requirements in...

Page 10: ...Voltage dip on 40 10 periods Test Level 2 40 10 periods Test Level 2 Comments Criterion C Criterion A Voltage dip on 0 1 period Test Level 2 0 1 period Test Level 2 Comments Criterion B Criterion B I...

Page 11: ...rself but replace it with an equivalent device Repairs may only be carried out by the manufacturer The manufacturer is not liable for damage resulting from violation CAUTION Before startup please ensu...

Page 12: ...The high voltage test is performed with a test voltage of at least 1 5 kV AC 2 2 kV DC or higher Routine manufacturing tests are inspected regularly by a certification body 6 3 High voltage dielectric...

Page 13: ...nsformer Filter Floating switching output 14 13 active PFC L N 13 14 active PFC No Description of the function elements 1 Connection terminal block input voltage Input L N 2 Connection terminal block...

Page 14: ...mm DIN rail The power supply can be aligned without minimum lateral clearance up to an ambient temperature of 40 C In a temperature range up to 70 C a lateral minimum clearance of 10 mm between two a...

Page 15: ...B D 105897_en_00 PHOENIX CONTACT 15 26 10 2 Device dimensions Figure 6 Device dimensions 160 167 130 45 80 TRIO POWER L N 13 14 10 24 30 68 78 11 11 5 42 9 40 5 3 5 8 5 7 5 Output 24V 10A DC Input AC...

Page 16: ...tion technology on the front The power supply is wired by simply plugging in the connecting cables no tools are required For the necessary connection parameters for the terminal blocks please refer to...

Page 17: ...ation of the device must correspond to EN 60950 regulations It must be possible to disconnect the device from the voltage using a suitable separator outside the power supply For example the primary si...

Page 18: ...e maximum output current or have separate protection The connecting cables on the secondary side should have large cross sections to keep the voltage drops in the cables as low as possible Figure 15 S...

Page 19: ...as prior to time point t1 If the request to supply the load still exists when the time intervals t2 to t3 have expired at least 7 s a new cyclical switching of the dynamic power reserve occurs to a t...

Page 20: ...The power supply can be operated at an installation height of up to 2000 m without any limitations Different data applies for installation locations above 2000 m due to the differing air pressure and...

Page 21: ...TRIO PS 2G 1AC 24DC 10 B D 105897_en_00 PHOENIX CONTACT 21 26 Normal mounting position Rotated mounting position 90 X axis Z X Y IN 1 5 x IN 25 0 10 20 30 40 50 60 70 80 C A...

Page 22: ...TRIO PS 2G 1AC 24DC 10 B D 105897_en_00 PHOENIX CONTACT 22 26 Rotated mounting position 180 X axis Rotated mounting position 270 X axis Z X Y IN 1 5 x IN 25 0 10 20 30 40 50 60 70 80 C A...

Page 23: ...C 10 B D 105897_en_00 PHOENIX CONTACT 23 26 Rotated mounting position 90 Z axis Rotated mounting position 270 Z axis Z X Y IN 1 5 x IN 25 0 10 20 30 40 50 60 70 80 C A Z X Y IN 1 5 x IN 25 0 10 20 30...

Page 24: ...mend that all cable connections from the power supply unit to the busbar are the same length and have the same cross section Depending on the system for parallel connection of more than two power supp...

Page 25: ...e case of n parallel connected devices Parallel connection for increasing power is used when extending existing systems A parallel connection is recommended if the power supply unit does not cover the...

Page 26: ...ship s bridge For use on the ship s bridge the DNV GL certified power supply meets the requirements of EMC protection class EMC B Thanks to special filtering measures magnetic or conducted noise emiss...