TRIO-PS-2G/3AC/24DC/40
105907_en_00
PHOENIX CONTACT
5 / 25
4
Technical data
Input data
Unless otherwise stated, all data applies for 25°C
ambient temperature, 400
V
AC input voltage, and nominal
output current (I
N
).
Input voltage range
3x 400 V AC ... 500 V AC -20 % ... +15 %
Network type
Star network
Frequency range (f
N
)
50 Hz ... 60 Hz
5
Hz
Current consumption (for nominal values) typ.
3x 1.9 A (400 V AC)
3x 1.7 A (500 V
AC)
Discharge current to PE
typ.
< 3.5 mA
< 2.5 mA (550 V AC, 60 Hz)
Mains buffering
> 10 ms (400 V AC)
> 20 ms (480 V AC)
Inrush surge current I
2
t
1.1 A
2
s
Switch-on current surge limitation typical after 1 ms
35 A
During the first few microseconds, the current flow into the filter capacitors is excluded.
Input fuse internal (device protection)
6.3 A
Choice of suitable circuit breakers
10 A ... 16 A (Characteristics B, C, D, K)
The external backup fuse must be approved for the (AC) supply voltage used and the voltage level.
Electric strength of the insulation
Insulation voltage input/output ( IEC/EN 60950-1 )
3 kV AC (type test)
1.5 kV AC (routine test)
Production test
2.5 kV DC