background image

1-999-2174   DATE: 1/04

OWNER’S GUIDE

USE AND CARE MANUAL 

UL Classified Industrial / 

Commercial Evaporative Air Cooler

Safety
Installation
Start-up

Operation
Maintenance
Trouble Shooting

%

Read all instructions carefully before installation.  

%

Use only the blower motor and circulating pump(s) 
combinations marked on the Model Nameplate indicating 
suitability for use in this model. Any other motors or pumps 
cannot be substituted.

%

Installation work and electrical wiring must be done by 
qualified person(s) in accordance with all applicable 
codes and standards, including fire rated construction.

%

When cutting or drilling into a wall or ceiling, do not 
damage electrical wiring or other concealed utilities (water 
or gas lines, sewer lines, etc.).

%

Cooler motor, pump, cabinet and junction box must be 
grounded in accordance with all local and national codes. 
A ground wire must be used between the power supply 
and the cooler.

%

Be sure that the cooler is connected to proper line voltage 
stamped on the pump and blower (fan) motor specification 
plate. NOTE: Improper voltage will void the pump and/or 
motor warranties and may cause serious personal injury 
or property damage.

%

Do not operate this blower (fan) motor with any solid-state 
speed control device.

!

Always disconnect electrical power to unit before 

working on or servicing cooler. More than one 
disconnect switch will be required to de-energize the 
equipment for servicing.

!

Do not remove pad frames while cooler is running, this 

may cause the blower (fan) motor to overload and 
damage the motor windings.

NOTE:

!

Do not locate unit near exhaust or vent pipes as odors or 
fumes may be drawn into cooler.

!

Use of anode devices, chemical additives or treatments in 
this cooler will void the warranty.

!

Your warranty does not cover shipping damage. Report all 
shipping damage at once to dealer or carrier making the 
delivery.

!

For future reference, record the model, serial numbers 
and installation date of your evaporative cooler here:

Model #   

 

Serial #

Install Date:

These Industrial / Commercial Evaporative Air Coolers are covered by 
the following City of Los Angeles (C.O.L.A.) Research Reports. 
Electrical: RR930159 (3/4, 1 & 1-1/2 Hp single phase applications), 
Mechanical: RR8075 (all applications)

WARNING -

 

TO REDUCE THE RISK OF FIRE, ELECTRIC 

SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING.

INSTALLER: Please deliver this guide to owner.

Congratulations: You have purchased a product of superior performance and design, which will give the best service when properly installed, operated and maintained. 

This guide was designed to provide you and your installer with information needed to mount, operate, inspect, maintain, and troubleshoot your Industrial / Commercial 
evaporative air cooler.

The first section, Installation and Start-Up, is especially for the installer. The second section, Regular Maintenance, contains operational and maintenance instructions for the 
owner and/or maintenance operations personnel, while Troubleshooting includes information on commonly encountered problems.

P

HOENIX 

M

ANUFACTURING, 

I

NC.

 

Installation and Start-up

Introduction

2

Mounting requirements

2

Location and placement

2

Duct systems

2

Exhaust openings

2

Electrical requirements

3

CONTENTS

Motor installation                            3
Pump junction box location            4
Motor pulley adjustment                 4
Belt adjustment                              4
Overflow standpipe installation      4
Water line connections                   4
Pump installation                            4

Bleed off  installation                      4
General inspections                       5
Pre - start - up                                5
Start-up Checklist                          5
Cabinet Inspection                         4

Maintenance

Cleaning                                     5-6

Draining and touch-up

6

Lubrication

6

Changing cooler pads

6

Pump mounting diagram

7

Troubleshooting

8

Summary of Contents for D8801

Page 1: ...tives or treatments in this cooler will void the warranty Your warranty does not cover shipping damage Report all shipping damage at once to dealer or carrier making the delivery For future reference...

Page 2: ...coolers are used to cool large areas such as factories auditoriums or supermarkets divide the area and strategically locate units of proper capacity in each area Install coolers in a location where on...

Page 3: ...with the installation location and installed in accordance with N E C Articles 240 and 430 These devices shall be U L Listed short circuit protection devices sized and installed in accordance with spe...

Page 4: ...and alignment is important proper setup reduces power consumption and prolongs life of belt and motor When installing or adjusting belt loosen the motor adjustment bolts and adjust to proper tension...

Page 5: ...ts Check torque on setscrews and cabinet hardware Motor and Blower Pulley set screws 95 in lbs Blower Wheel set screws 1 per side 150 in lbs Cabinet hardware 25 in lbs GENERAL INSPECTION Initial Start...

Page 6: ...otor blower assembly Check belt condition and replace it if frays or cracks appear Check alignment of blower pulley with motor pulley Cleaning Water Pump Hose CAUTION Disconnect all electrical power t...

Page 7: ...sition pump as shown for your specific model make sure pump sits flat on bottom Bend bracket as required to conform to the mounting surface Using slotted holes in bracket as a guide mark and drill two...

Page 8: ...xcessive humidity inside Musty or unpleasant odor POSSIBLE CAUSE 1 No electrical power to unit A Fuse blown B Circuit breaker tripped 2 Belt loose or broken 3 Motor overloaded and or frozen bearings A...