Figure 7: Sensor connected to a dry contact input]
Any N.O. or N.C. sensor can be attached to the WTU-14 using 18–
24 gauge wire. For distances of 1000' or more, use heavier gauge
wire. When running wire outdoors it is recommended that shielded
cable be used. Connect the shield to a good earth ground or metallic
cold water pipe. The total resistance of the circuit cannot be greater
than 100 ohms. Use wire appropriate for the application. See the
wire length recommendations, later in this chapter.
The WTU-14 may have more than one sensor connected to the same
terminal, however, the normal condition for each sensor on the same
terminal must be identical (either all N.O. or all N.C.).
Normally Closed Sensors
To wire more than one normally closed sensor on one input, they
must be connected in series. Connect a lead from the first sensor to
one of the Dry Contact Inputs on the terminal strip. Next, take the
other lead from the first sensor and connect it to one lead from the
next sensor. Continue connecting sensors end-to-end until you have
connected all of your sensors. Take the second lead from your last
sensor and connect it to the ground screw on the WTU-14 terminal
strip. See Figure 8.
Multiple N.C. inputs are typically magnetic reed switches to moni-
tor the security of windows and doors.
Chapter 2: Installation
29
Summary of Contents for Skymetry WTU-14
Page 1: ...WTU 14 User s Manual version 1 11 Phonetics Inc LIT 0085...
Page 5: ...v...
Page 14: ...Skymetry WTU 14 Manual xiv...
Page 20: ...Skymetry WTU 14 Manual 20...
Page 32: ...Figure 11 A thermistor and a 4 20mA transducer connected to the unit Skymetry WTU 14 Manual 32...
Page 48: ...Skymetry WTU 14 Manual 48...
Page 52: ...Skymetry WTU 14 Manual 52...
Page 58: ...Skymetry WTU 14 Manual 58...
Page 64: ...Skymetry WTU 14 Manual 64...
Page 82: ...Skymetry WTU 14 Manual 82...
Page 86: ...Skymetry WTU 14 Manual 86...
Page 90: ...Skymetry WTU 14 Manual 90...
Page 98: ...Skymetry WTU 14 Manual 98...
Page 100: ...Skymetry WTU 14 Manual 100...
Page 106: ...Skymetry WTU 14 Manual 106...
Page 108: ...Skymetry WTU 14 Manual 108...
Page 109: ...Test Log...
Page 110: ......