Battery Input
Battery monitoring is a built-in function. The unit will go into alarm
when the battery level drops below 12.0V for the programmed rec-
ognition time. In this state the Battery LED will blink.
Special Function Inputs
When the Skymetry WTU-14 is used for Pump Control, several of
the inputs are dedicated to a specific task depending on whether
Dry Contact
or
Analog Level
is selected as the Pump Control
method. The tables below identify which inputs are used and what
function they serve. Refer to the Pump Control chapter for more
information.
Dry Contact Fill/Drain Pump Control
Dry Contact Input #6 – Lead pump float switch
Dry Contact Input #7 – Lag pump float switch
Dry Contact Input #8 – All pumps off float switch
Analog Level Fill/Drain Pump Control
Analog Input #6 – connect to analog (4–20mA) level sensor
Chapter 4: Input Programming
47
Summary of Contents for Skymetry WTU-14
Page 1: ...WTU 14 User s Manual version 1 11 Phonetics Inc LIT 0085...
Page 5: ...v...
Page 14: ...Skymetry WTU 14 Manual xiv...
Page 20: ...Skymetry WTU 14 Manual 20...
Page 32: ...Figure 11 A thermistor and a 4 20mA transducer connected to the unit Skymetry WTU 14 Manual 32...
Page 48: ...Skymetry WTU 14 Manual 48...
Page 52: ...Skymetry WTU 14 Manual 52...
Page 58: ...Skymetry WTU 14 Manual 58...
Page 64: ...Skymetry WTU 14 Manual 64...
Page 82: ...Skymetry WTU 14 Manual 82...
Page 86: ...Skymetry WTU 14 Manual 86...
Page 90: ...Skymetry WTU 14 Manual 90...
Page 98: ...Skymetry WTU 14 Manual 98...
Page 100: ...Skymetry WTU 14 Manual 100...
Page 106: ...Skymetry WTU 14 Manual 106...
Page 108: ...Skymetry WTU 14 Manual 108...
Page 109: ...Test Log...
Page 110: ......