Why don’t the values displayed on the web page match
the values displayed in the Skymetry software?
• The web page displays a snapshot of the values at a particular
moment in time. It does not display real-time values, as is the
case when connected locally through the Skymetry software.
• Click the
Status Update
button on the web page to retrieve a
current snapshot.
Why can’t I get pump control to work?
• The Output(s) are not set to
Pump Control
mode.
• The Pump Control parameters are programmed incorrectly.
• The level transducer is not wired to analog input #6.
• The level transducer is not reading the proper values.
• The float switches are not wired to Dry Contact inputs #6, #7,
and #8.
• The float switches are not
Normally Open
.
• The
Lead
,
Lag
, and
Pumps-Off
float switches are not wired to
the proper inputs.
Appendix B: Troubleshooting
97
Summary of Contents for Skymetry WTU-14
Page 1: ...WTU 14 User s Manual version 1 11 Phonetics Inc LIT 0085...
Page 5: ...v...
Page 14: ...Skymetry WTU 14 Manual xiv...
Page 20: ...Skymetry WTU 14 Manual 20...
Page 32: ...Figure 11 A thermistor and a 4 20mA transducer connected to the unit Skymetry WTU 14 Manual 32...
Page 48: ...Skymetry WTU 14 Manual 48...
Page 52: ...Skymetry WTU 14 Manual 52...
Page 58: ...Skymetry WTU 14 Manual 58...
Page 64: ...Skymetry WTU 14 Manual 64...
Page 82: ...Skymetry WTU 14 Manual 82...
Page 86: ...Skymetry WTU 14 Manual 86...
Page 90: ...Skymetry WTU 14 Manual 90...
Page 98: ...Skymetry WTU 14 Manual 98...
Page 100: ...Skymetry WTU 14 Manual 100...
Page 106: ...Skymetry WTU 14 Manual 106...
Page 108: ...Skymetry WTU 14 Manual 108...
Page 109: ...Test Log...
Page 110: ......