STEP III
WIRING YOUR AC MODULES
CAUTION!
Utility connection of this unit must be performed by a licensed
electrician or other qualified personnel. Read these instructions completely
before proceeding with installation.
If you do not understand the instructions or steps required herein, seek assistance from
qualified personnel.
Additional information required for installation may be found in the National Fire Protection
Association Publication NFPA70, known as the National Electrical Code., any state building
codes, and any applicable local codes.
The following instructions are intended to be used in conjunction with AC Module Installation
Figures on the following pages. To ensure a safe, reliable installation, please comply with the
instructions as specified, and in the order presented.
CAUTION!
Ensure AC conductors have no voltage present. Open all AC
circuit breakers and verify zero volts are present before proceeding!
NOTE!
Use only the fasteners provided to mount the AC Modules. Use of
any other hardware is not recommended and may lead to unsafe operation of
your AC Modules.
NOTE!
For exterior installations where conduit may be used, weather-tight
conduit fittings complying with requirements in the “Standard for Fittings for
Conduit and Outlet Boxes, UL 514B”, must be used. In such event, install
conduit couplings as required by your local Electrical Code.
WARNING! Before proceeding, ensure the steps below have been performed:
Disconnect AC Power from any point of attachment prior to connecting AC
Modules.
CAUTION! To reduce the risk of fire, connect only to a dedicated circuit
provided with 20 amperes maximum branch-circuit over-current protection in
accordance with the National Electrical Code, ANSI/NFPA 70.