background image

 
 
EDF ENR PWT 

 

 

 

 

 

 

 

D06

P06

01

   

Indice

 

1

   

Date:

   

3

01

13

 

EDF

 

ENR

 

PWT

 

 

Société

 

par

 

actions

 

simplifiée

 

à

 

associé

 

unique

 

 

au

 

capital

 

de

 

37

 

505

 

000

 

 ‐ 

 

513

 

281

 

972

 

RCS

 

NANTERRE

 

Siège

 

social

 

:

 

100

 

Esplanade

 

du

 

Général

 

de

 

Gaulle

 

 

Cœur

 

Défense

 

 

Tour

 

B

 

92932

 

Paris

 

La

 

Défense

 

cedex

.

 

33,

 

Rue

 

Saint

 

Honoré

 ‐ 

Z.I.

 

Champfleuri

   

38300

 

Bourgoin

 

Jallieu

 ‐ 

France

 

Tel

 

:

 

04

 

74

 

93

 

80

 

20

 ‐ 

Fax

 

:

 

04

 

74

 

93

 

80

 

40

 

 

Use a torque wrench for installation. The above figure shows methods of fastening module to support 

structure. Tightening torques should respectively be within 4~6 Nm and 10~17 Nm for M6x1 (Example A) 

and M8x1.5 (Example B) coarse thread bolts, depending on bolt class. Different recommendations from 

specific clamping hardware suppliers should prevail. 

 

 

Photowatt modules can be installed in either landscape or portrait position, refer to the detailed instructions 

in table 2 for further guidance. Note that further countermeasures such as the use of additional support bars 

should be considered in heavy snow areas (> 2400 Pa), to avoid damage by the snow accumulating in the 

lowest row of modules. 

 

Method A: Bolting   

 

Modules should be bolted to support structures through mounting holes located in the frame's back flanges 

only. Do not drill additional holes or modify the module frame. Doing so will void the warranty.   

 

Each module must be securely fastened at a minimum of 4 points on two opposite sides. If additional wind 

loads are anticipated for this installation, additional mounting points should be used. System designer and 

installer are responsible for load calculation and for proper support structure design.   

 

Modules should be bolted at the following hole locations depending on the configuration and load: 

Table 2: Authorized attachments for bolting/clamping method 

 

Bolting/clamping on short side frame

 

Bolting/clamping on long side frame 

Uplift load   

 2400 Pa   

 

Downforce load 

 5400 Pa   

Use 4 standard mounting holes (short side) 

 

Use 4 standard mounting holes (long side) 

Method B: Clamping 

 

Top or bottom clamping methods will vary depending on mounting structures. Follow mounting guidelines 

recommended by the mounting system supplier. 

 

The clamps should be positioned according to table 2, using the mounting holes as reference locators then 

install and tighten the module clamps to the torque stated by the mounting hardware manufacturer.   

 

EDF ENR PWT’s limited warranty will be void in cases where improper clamps or installation methods 

deviating from this manual are used. When installing inter-modules or end type clamps, take measures so 

as: 

 

1.

 

Not to bend the module frame 

2.

 

Not to touch or cast shadow on the front glass 

3.

 

Not to damage the surface of the frame 

4.

 

To ensure the clamps overlap the module frame by at least 9 mm 

8

Summary of Contents for EDF ENR PWT

Page 1: ...hese instructions may result in death injury or property damage The installation of solar modules requires specialized skills and should only be performed by licensed professionals The word module or...

Page 2: ...aterial to halt production of electricity when installing or working with a module or wiring Do not install or handle the modules when they are wet or during periods of high wind Do not use or install...

Page 3: ...n factors table for open circuit voltage 4 0 STORAGE AND UNPACKING Precautions and General Safety Store modules in a dry and ventilated room Do not allow children and unauthorized persons near the ins...

Page 4: ...s please ensure the assembly is mounted over a fire resistant roof covering rated for the application Photowatt modules have been listed as Class C according to UL790 standard PW series solar modules...

Page 5: ...fixed in place in a manner suitable to withstand all expected loads including wind and snow loads A minimum clearance of 6 5 mm 1 4 of an inch or more between modules is required to allow for thermal...

Page 6: ...r M5 size SS cup washer and M5 size SS nut with teeth is used to attach a copper grounding wire to grounding hole on the frame see picture above Attach the wire between the flat washer and the cup was...

Page 7: ...g holes short side 6 Module frame 7 Cables and connectors The mounting design must be certified by a registered professional engineer The mounting design and procedures shall comply with local electri...

Page 8: ...will void the warranty Each module must be securely fastened at a minimum of 4 points on two opposite sides If additional wind loads are anticipated for this installation additional mounting points s...

Page 9: ...local fire building and electrical codes Ensure that they are in perfect electrical and mechanical condition The permitted type of solar cable is single conductor 2 5 10 mm2 8 14 AWG 90 C wet rated w...

Page 10: ...ance Tel 04 74 93 80 20 Fax 04 74 93 80 40 ANNEX MECHANICALAND ELECTRICAL RATINGS Standard Test Conditions are irradiance of 1 kW m2 AM1 5 spectrum and cell temperature of 25 C Pmax of any individual...

Reviews: