background image

EDF ENR PWT 

 

33,

 

Rue

 

Saint

 

Honoré

 ‐ 

Z.I.

 

Champfleuri

 

 

38300

 

Bourgoin

 

Jallieu

 ‐ 

France

 

Tel

 

:

 

33

 

4

 

74

 

93

 

80

 

20

 ‐ 

Fax

 

:

 

33

 

4

 

74

 

93

 

80

 

40

 

 

EDF

 

ENR

 

PWT

 

 

Société

 

par

 

actions

 

simplifiée

 

à

 

associé

 

unique

 

 

au

 

capital

 

de

 

37

 

505

 

000

 

 ‐ 

 

513

 

281

 

972

 

RCS

 

NANTERRE

 

Siège

 

social

 

:

 

100

 

Esplanade

 

du

 

Général

 

de

 

Gaulle

 

 

Cœur

 

Défense

 

 

Tour

 

B

 

92932

 

Paris

 

La

 

Défense

 

cedex

.

 

D07-P0

6-01

 GB
 

 

 

Ind
ice
 1

 

   Date 

3

-01-13

 

Cables and connectors 

 

The mounting design must be certified by a registered professional engineer. The mounting design and 
procedures shall comply with local electrical and building codes. 

 

The module is considered to be in compliance with UL 1703 only when the module is mounted in the 
manner specified by the mounting instructions below. 

 

Mounting hardware is not provided by EDF ENR PWT. 

 

EDF ENR PWT modules can be mounted to a support structure by several approved methods, either using 
the mounting holes located on the back frame (see Example A), or by means of clamps (see Example B). 
For other installation hardware, please contact your local representative for further information. Failure to 
use a recognized installation method will void EDF ENR PWT warranty.   

 

Only the bolting method has been qualified by all major North-American certification bodies (CSA, and 
Intertek) during testing and listing of EDF ENR PWT modules according to UL1703 standard. For 
inlay-systems or other installation hardware, please contact your local representative for further information. 
Alternative mounting methods qualified internally by EDF ENR PWT are described in Annex C. 

Example A:

   

 

 

 

 

 

 

 

Example B:

   

Bolting (INTERTEK and CSA qualified) 

         

Clamping on (INTERTEK qualified) 

               

           

 

Use appropriate corrosion-proof fastening materials. All mounting hardware (bolt/spring washer/flat 
washer/nut) should be made with stainless steel M6 size for bolting method (A), and M8 size for clamping 
method (B).     

 

Use a torque wrench for installation. The above figure shows methods of fastening module to support 
structure. Tightening torques should respectively be within 4~6 Nm and 10~17 Nm for M6x1 (Example A) 
and M8x1.5 (Example B) coarse thread bolts, depending on bolt class. Different recommendations from 
specific clamping hardware suppliers should prevail. 

 

EDF ENR PWT modules can be installed in either landscape or portrait position, refer to the detailed 
instructions (see table 6-1) for further guidance. Note that further countermeasures such the use of 
additional support bars should be considered in heavy snow areas (> 2400 Pa), to avoid damage by the snow 
accumulating in the lowest row of modules. 

 

When the addition of a support bar is recommended to enhance mechanical stability and module long term 
performance reliability, material of suitable resistance should be selected. EDF ENR PWT recommends a 
minimum thickness of 50mm for the bar. The support bar centerline should be positioned within 100 mm of 
the side frame centerline (slight shift may be necessary to access module grounding hole). 

6.1 MOUNTING METHOD: BOLTING 

 

Modules should be bolted to support structures through mounting holes located in the frame's back flanges 
only. Do not drill additional holes or modify the module frame. Doing so will void the warranty.   

 

Each module must be securely fastened at a minimum of 4 points on two opposite sides, using the most 
inner mounting holes. If additional wind loads are anticipated for this installation, additional mounting 

Summary of Contents for PW2350 UL Series

Page 1: ...ax 33 4 74 93 80 40 EDF ENR PWT Soci t par actions simplifi e associ unique au capital de 37 505 000 N 513 281 972 RCS NANTERRE Si ge social 100 Esplanade du G n ral de Gaulle C ur D fense Tour B 9293...

Page 2: ...ling system installation or compliance or non compliance with the instructions set forth in this manual 2 0 SAFETY PRECAUTIONS Warning All instructions should be read and understood before attempting...

Page 3: ...ith an AM1 5 spectrum and cell temperature of 25 C The detailed electrical and mechanical characteristics of EDF ENR PWT crystalline silicon PV modules can be found in table A 2 of this manual see Ann...

Page 4: ...with sharp objects as scratches may directly affect product safety Do not leave a module unsupported or unsecured Do not change the wiring of bypass diodes Keep all electrical contacts clean and dry 5...

Page 5: ...ted together to create a voltage higher than the permitted maximum system voltage even under the worst local temperature conditions Similar electrical performance modules should be connected in the sa...

Page 6: ...op and ensure conductor ampacity complies with local regulations such as NEC 690 8 D Cable protection Secure the cables to the mounting system using UV resistant cable ties Protect exposed cables from...

Page 7: ...ed for Photowatt modules as described below For alternative CSA qualified grounding methods please refer to Annex B Method Bolt Nut with teeth Cup washer When diameter of the grounding holes is 5mm CS...

Page 8: ...lified Clamping on INTERTEK qualified Use appropriate corrosion proof fastening materials All mounting hardware bolt spring washer flat washer nut should be made with stainless steel M6 size for bolti...

Page 9: ...below the module Mounting rails should run parallel to the short side frame Bolting on long side frame Use 4 standard mounting holes long side Mounting rails may run perpendicularly or parallel to the...

Page 10: ...pecifications are subject to change without notice Table A Specifications for PW series photovoltaic modules under STC PW2350 UL Typical power Pmax W 220 225 230 235 240 Voltage at typical power Vmp V...

Page 11: ...r Vmp V 35 8 35 9 36 0 36 1 36 3 Current at typical power Imp A 7 96 8 08 8 19 8 30 8 41 Open circuit voltage Voc V 44 3 44 4 44 5 44 6 44 8 Short circuit current Isc A 8 53 8 64 8 76 8 87 8 97 Power...

Page 12: ...le Once crimped each terminal should be visually checked according to the following points 1 The insulator jacket is correctly crimped in the first collar 2 The conductor core is correctly crimped in...

Page 13: ...r cast shadow on the front glass 3 Not to damage the surface of the frame 4 To ensure the clamps overlap the module frame by at least 5 mm 5 To ensure the clamps overlap length is at least 40 mm Clamp...

Page 14: ...SYSTEMS The mounting method has been qualified by EDF ENR PWT and certified by CSA Insertion methods will vary and are dependent on the mounting structures Follow mounting guidelines recommended by t...

Page 15: ...Pa Downforce load 2400 Pa Uplift load 2400 Pa 2400 Pa Downforce load 4000 Pa Insertion profile on short side frame Use 2 insertion profiles running parallel to the short side frame Use 2 insertion pr...

Reviews: