D81-P06-01 GB R5
28/07/2020
www.photowatt.com
5
PRODUCT IDENTIFICATION
•
Each module has two identical barcodes (one
in the laminate under the front glass, the se-
cond on the rear side of the module) that act as
a unique identifier. Each module has a unique
serial number containing 14 digits.
•
A nameplate is also affixed to the rear glass
of each module. This nameplate specifies the
model type, as well as the main electrical and
safety characteristics of the module.
5.0
MODULE INSTALLATION
PRECAUTIONARY MEASURES AND
GENERAL SAFETY
•
Prior to installing modules please obtain infor-
mation about any requirements and necessary
approvals for the site, installation and inspection
from the relevant authorities.
•
Check applicable building codes to ensure that
the construction or structure (roof, facade, sup-
port, etc.) can bear the module system load.
•
Aluminum frame solar modules have been quali-
fied for Application Class A (equivalent to Safety
Class II requirements). Modules rated under this
class should be used in systems operating at vol-
tage above 50 V or power above 240 W, where
general contact access is anticipated.
•
EDF ENR PWT double glass modules have been
certified as Type 3 or Type 13 according to UL
1703 and as Class A for fire performance accor-
ding to IEC 61730-2, please refer to the datasheet
or the product nameplate for the detailed types.
•
Consult your local authority for guidelines and
requirements for building or structural fire safety.
UL 1703 SYSTEM FIRE RATING REQUIREMENTS
•
A photovoltaic system composed of UL1703
certified modules mounted on a UL2703 cer-
tified mounting system should be evaluated in
combination with roof coverings in accordance
with UL1703 standard, with respect to meeting
the same fire classification as the roof assembly.
•
Mounting systems with a System Fire Class Ra-
ting (Class A, B or C), tested in conjunction with
fire rated “Type 3” or “Type 13” rated modules,
are considered acceptable for use with Cana-
dian Solar Inc. modules, provided the mounting
system does not violate any other requirement
of this manual.
•
Any mounting system limitation on inclination
or accessory required to maintain a specific
System Fire Class Rating should be clearly spe-
cified in the installation instructions and UL2703
certification of the mounting system supplier.
•
The fire rating for this module is only valid
when the product is installed as specified in the
mechanical mounting instructions.
•
When installing the modules on rooftop, ensure
the assembly is mounted over a fire resistant
roof covering rated for the application.
ENVIRONMENTAL CONDITIONS
•
The module is intended for use in general open-
air climates, as defined in IEC 60721-2-1: Clas-
sification of environmental conditions Part 2-1:
Environmental conditions appearing in nature
- temperature and humidity.
•
Please consult the EDF ENR PWT technical sup-
port department for more information on the
use of modules in special climates.
•
Do not install modules near open flames or
flammable materials.
•
Do not immerse modules in water or constantly
expose modules to water (either fresh or salt)
(i.e. from fountains, sea spray).
•
Exposing modules to salt (i.e. marine environ-
ments) or sulfur (i.e. sulfur sources, volcanoes)
incurs the risk of module corrosion.
• Failure to comply with these instructions will
void EDF ENR PWT warranty.
INSTALLATION REQUIREMENTS
•
Ensure that the module meets the general tech-
nical system requirements.
•
Ensure that other systems components do not
damage modules mechanically or electrically.
•
Modules can be wired in series to increase
•
voltage or in parallel to increase current. To
connect modules in series, connect the cables
from the positive terminal of one module to
the negative terminal of the next module. To
connect in parallel, connect the cables from
the positive terminal of one module to the posi-
tive terminal on the next module.
•
The quantity of bypass diodes in the module’s
junction box provided may vary depending on
the model series.
•
Only connect the quantity of modules that cor-
responds to the voltage specifications of the in-
verters used in the system. In addition modules
must NOT be connected together to create a
voltage higher than the maximum permitted
system voltage stated on the module name-
plate, even under the worst local temperature
conditions (see Table 1 for the correction coeffi-
cients that apply to open-circuit voltage).
•
A maximum of two strings can be connected in
parallel without using over-current protection
device (fuses, etc.) incorporated in series wit-
Summary of Contents for PW60HT-C-XF
Page 1: ...INSTALLATION MANUALS For professional use only...
Page 2: ...INSTALLATION MANUAL FOR STANDARD MODULES For professional use only...
Page 27: ...INSTALLATION MANUAL OF DOUBLE GLASS MODULES For professional use only...
Page 42: ...INSTALLATION MANUAL OF BIFACIAL MODULES For professional use only...