CABLE AND CONNECTOR PROTECTION
•
Secure the cables to the mounting system
using UVresistant cable ties. Protect exposed
cables from damage by taking appropriate pre-
cautions (e.g. placing them inside a metallic
raceway like EMT conduit). Avoid exposure to
direct sunlight.
•
A minimum bending radius of 60mm (2.36 in) is
required when securing the junction box cables
to the racking system.
•
Do not place connectors in locations where wa-
ter could easily accumulate.
5.2
GROUNDING
•
For grounding requirements in North Ameri-
ca, a module with exposed conductive parts is
considered to comply with UL 1703 only when
it is electrically grounded in accordance with
both the instructions presented below and the
requirements of the National Electrical Code.
Any grounding means used with Canadian So-
lar Inc. modules should be NRTL certified to UL
467 and UL 2703 standards. Please consult our
technical service team for the formal approval
process.
•
For grounding requirements in other areas, al-
though the modules are certified to Safety
Class II, we recommend them to be grounded
and that module installation should comply
with all applicable local electrical codes and re-
gulations. Grounding connections should be
installed by a qualified electrician. Connect mo-
dule frames together using adequate groun-
ding cables: we recommend using 4-14 mm²
(AWG 6-12) copper wire. Holes provided for this
purpose are identified with a grounding symbol
All conductive connection junctions must
be firmly fixed.
•
Do not drill any extra ground holes for conve-
nience as this will void the modules warranty.
•
All bolts, nuts, flat washers, lock washers and
other relevant hardware should be made of
stainless steel, unless otherwise specified.
•
EDF ENR PWT does not provide grounding hard-
ware.
•
One grounding method is recommended for
EDF ENR PWT standard modules, as descri-
bed below. For alternative grounding methods,
please refer to Annex B (Alternative Grounding
Methods).
GROUNDING METHOD:
BOLT + TOOTHED NUT + CUP WASHER
•
A grounding kit containing an M5 (3/16") SS cap
bolt, an M5 (3/16") SS flat washer, an M5 (3/16")
SS cup washer, and an M5 (3/16") SS nut (with
teeth) is used to attach copper grounding wire
to a pre-drilled grounding hole on the frame
(see image above).
•
Place the wire between the flat washer and the
cup washer. Ensure that the cup washer is po-
sitioned between the frame and the wire with
the concave side up to prevent galvanic cor-
rosion. Tighten the bolt securely using the SS
toothed nut. A wrench may be used to do this.
The tightening torque is 3-7 Nm (2.2-5.2 ft-lbs).
6.0
MOUNTING INSTRUCTIONS
•
The mounting design must be certified by a re-
gistered professional engineer. The mounting
design and procedures must comply with local
codes and requirements from all relevant autho-
rities. The module is considered to be in com-
pliance with UL 1703 and IEC 61215 only when
the module is mounted in the manner specified
by the mounting instructions included in this
installation manual.
•
Any module without a frame (laminate) shall not
be considered to comply with the requirements
of UL 1703 unless the module is mounted with
hardware that has been tested and evaluated
with the module under this standard or by a field
Inspection certifying that the installed module
complies with the requirements of UL 1703.
•
EDF ENR PWT does not provide mounting hard-
ware.
•
Standard modules can be mounted onto a sup-
port structure using one of several approved
methods. One of such mounting methods is
described below. For details of other mounting
methods and the methods recommended by
EDF ENR PWT for special module ranges, please
refer to the Annex A (Alternative Mounting Me-
thods). For information about other installation
methods, please contact your local representa-
tive. Failure to use a recognized installation me-
thod will void the EDF ENR PWT warranty.
•
Use appropriate corrosion-proof fastening ma-
terials. All mounting hardware (bolts, spring
washers, flat washers, nuts) should be hot dip
galvanized or stainless steel.
•
Use a torque wrench for installation.
•
Do not drill additional holes or modify the mo-
dule frame.
•
Doing so will void the warranty.
Summary of Contents for PW60HT-C-XF
Page 1: ...INSTALLATION MANUALS For professional use only...
Page 2: ...INSTALLATION MANUAL FOR STANDARD MODULES For professional use only...
Page 27: ...INSTALLATION MANUAL OF DOUBLE GLASS MODULES For professional use only...
Page 42: ...INSTALLATION MANUAL OF BIFACIAL MODULES For professional use only...