5 Installation
P-62x Positioners
PZ234D
Version: 1.2.0
25
Fixing the P-62x and the load
1.
Alignment (optional):
−
Align the positioner to the locating holes (p. 48) in the base body and suitable
dowel pins.
−
Align the load with the help of suitable dowel pins and the locating holes (p. 48) in
the platform of the P-62x.
2.
Fixing:
−
Fix the positioner with the help of suitable dowel pins and the mounting holes
(p. 48) provided. If the positioner is not equipped with a separate protective earth
connector, follow the instructions for connecting the protective earth conductor via
the mounting holes (p. 25) when fixing the positioner.
−
Fix loads by tightening the screws in the threaded holes (p. 48) provided.
5.3
Connecting the P-62x to the Protective Earth Conductor
INFORMATION
In the case of P-62x positioners with D-sub connectors, ground loops can occur when the
positioner is grounded via its protective earth connector as well as via the connecting cable's
shielding for the electronics.
If a ground loop occurs, contact our customer service department (p. 39).
INFORMATION
Pay attention to the applicable standards for connecting the protective earth conductor.
The connection of the P-62x to the protective earth conductor depends on the model:
Models
with
separate protective earth connector (all except P-620 and P-621.2xx/.2U)
Models
without
separate protective earth connector (P-620 and P-621.2xx/.2U only)
Separate protective earth connector available
If a separate protective earth connector is available, it must be used.
Figure 6: Threaded hole for protective earth connection