15.4. VOC/eCO2 control
The room air quality is measured via VOC and eCO2 sensors, and the air volume flow is controlled in a demand-oriented fashion. In
the automatic mode, the ventilation unit regulates the air volume flow as a function of the air quality (VOC) or the eCO2 values on a
needs-based basis. The greater the value, the larger the volume flow.
Acceptable room air should not exceed a CO2 value of approx. 1000 ppm and have air quality class 1 to 2.
Room air quality/
IAQ rating
Reference Level
TVOC (mg/m
3
)
Air quality
< 2.0
Level 1
< 0.3
Very good
2.0 to 2.99
Level 2
0.3 to 1.0
Good
3.0 to 3.99
Level 3
1.0 to 3.0
Medium
4.0 to 4.99
Level 4
3.0 to 10
Poor
5.0
Level 5
> 10
Bad
CO
2
co
ncent
ra
ti
on
in
pp
m
Decreasing
power of
concentration,
headaches
Disruptive
Pleasant
Closed window
Mech. domestic ventilation
Fresh outdoor air: 400 ppm
Hours
Ambient temperature in °C
Still comfortable
Comfortable
Uncomfortably dry
Uncomfortably damp
Based on Leusden und Freymark
Graphics: www.komfortlüftunq.at
R
elat
ive
hum
idi
ty
(
R
H
)
of
the
am
bi
ent
air
in
%
Structural-physical upper limit
(condensate, mildew ...) approx.
45 % to 55 %
Ideal 35 % to 45 % RH
Lower comfort limit for humans 20 %
15.5. Outdoor air quality control
If the ventilation unit has been configured by the factory with an (optional) VOC/eCO2 sensor in the outdoor air, the function can be
activated via the APP. If the outdoor air quality (VOC value) is less than class 4 for a certain time, the ventilation unit changes to the
Standby mode. After approx. one hour in standby operation, the ventilation unit is restarted automatically.