V05-060619
LORA
TM
COMMUNICATION
The device comes equipped with LoRa
TM
radio technology wireless communication for private networks. These devices are only for
private networks and can’t be connected to LoRaWAN networks. By default,
Bridge LR
is configured in
slave mode
.
The frequency for Europe is free ISM band 868 MHz but the device incorporates 9 different channels between 865,1 MHz (channel
0) and 869,85 MHz (channel 9). Default frequency is fixed to 869,525 MHz (channel 7).
In reference to
transmission and reception mode
, the device includes 10 modes to choose between 300 bps and 21875 bps
considering that increasing bitrate affects to signals coverage.
In order to comply the spectral limitation, depends on transmission mode configured in the master, a silence time will be
established. During this time, the device won’t be able to transmit and that will be displayed with RF led fixed on blue and returning
“Busy” via serial port.
CONFIGURATION OF THE DEVICE
To configure Bridge LR you must download the PC software from
PickData’s
website. You will be able to configure any RS-485 Modbus and LoRa
parameter, set subnetworks and verify communications.
For advanced configuration download the manual of the product at
PickData’s website.
INSTALLATION
Bridge LR 230 VAC
has been designed for DIN rail mounting.
IMPORTANT
Take into account that when the device is connected, the terminals may be hazardous to the touch, and opening
the covers or removing elements may provide access to parts that are dangerous to the touch. Do not use the
device until it is fully installed
SAFETY PRECAUTIONS
DANGER
Warns of a risk, which could result in personal injury or material damage caused by an incorrect handling or
installation of the unit. In particular, handling with voltages applied may result in electric shock, which may cause
death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of fi re. Read
the manual carefully prior to connecting the unit. Follow all installation and maintenance instructions throughout
the unit’s working life. Pay special attention to the installation standards of the National Electrical Code.
DISCLAIMER
PickData, SL reserves the right to make modifications to the device or the unit specifications set out in this instruction manual
without prior notice.
PickData, SL on its web site, supplies its customers with the latest versions of the device specifications and the most updated
manuals.
MAINTENANCE AND TECHNICAL SERVICE
Device doesn’t require maintenance.
In the case of any query in relation to unit operation or malfunction, please contact the PickData, SL technical support service.
PickData, SL
– Technical support service
Calle Innovació, 3
08232
– Viladecavalls (Barcelona), SPAIN
Tel: (34) 935 117 505 (España)
Email: