53
ID
Class
Designation
(Possible) cause/effect
Rectification/action
Quit
610 Error
Mixer group
The mixer group of the heating circuit is
defective. The heating circuit is not ready for
operation.
The mixer group (inflow
temperature, pump,
mixer) of the heating
circuit must be checked.
No
611 Warning Sensor room
temperature
The room temperature sensor is defective.
The inflow temperature is determined based
on the exterior temperature and a supposed
room temperature of 20,0° C.
The exhaust gas
temperature sensor or its
wiring must be checked.
No
612 Warning Digital remote control
An invalid value was received by the digital
remote control (DRC). The values of the DRC
are ignored.
The DRC must be
checked.
No
613 Error
Pump heating circuit
The pump of the heating circuit is defective.
The heating circuit is not ready for operation.
The pump of the heating
circuit must be checked.
No
614 Error
Heating circuit
deactivated
An incorrect parameter setting was found
during the start-up process. The heating
circuit is not active.
Check and correct
assigned parameters.
Restart system.
Yes
615 Warning Screed Drying
Screed drying settings have to be checked
before resuming. Screed drying is not started
until confirmation.
Confirm message
Yes
616 Warning Sensor room humidity
The humidity room sensor is defect.
Cooling function is deactivated.
The humidity room sensor
and its wiring must be
proved.
No
617 Warning Sensor reflux
temperature
Reflux temperature sensor is broken.
Reflux supervision is disabled.
Reflux temperature
sensor and its wiring has
to be checked.
No
700 Error
Sensor collector
temperature
The temperature sensor collector is defective.
The solar system is not ready for operation.
The sensor or its wiring
must be checked.
No
701 Error
Sensor flow
temperature
The inflow temperature sensor for the heat
volume of the solar system is defective. .
The heat volume cannot be calculated.
The sensor or its wiring
must be checked.
No
702 Error
Sensor reflux
temperature
he reflux temperature sensor for the heat
volume of the solar system is defective.
The sensor or its wiring
must be checked.
No