● 200-240VAC, 50–60Hz, 30A
● 230VAC, 16A or 32A (Europe)
● WYE-connected 3-phase:
○ USA: 120/208VAC, 50-60Hz, 30A
○ Europe: 230/400VAC, 50-60Hz, 16A
The total power required by a rack depends on the number and type of hardware
that is in the rack.
System Environmentals
Table 48 System altitude specifications
Mode
Elevation
Operational
-200 to 10,000 feet (-61 to 3048 meters)
Non-
operational
-200 to 40,000 feet (-61 to 12,192 meters)
Table 49 System temperature and humidity specifications
Mode
Ambient
temperature
Non-
condensing
humidity
Max wet bulb
temperature
Gradient
Operational
Up to 7000
feet elevation:
+41 to 104°F
(+5 to 40°C)
Up to 10,000
feet elevation:
+41 to 95°F
(+5 to 35°C)
10–85%
10%/hr
gradient
86°F
(30°C)
36°F/hr
(20°C/hr)
Non-
operational
-22 to 158 °F
(-30 to 70 °C)
5–95%
104°F
(40°C)
54°F/hr
(30°C/hr)
Appendix C Pillar Axiom Hardware Specifications
About Pillar Axiom 600 Hardware Specifications
180