Table 67 Rack specifications for a Pillar Axiom 600 system (continued)
Criteria
Pillar rack
Non-Pillar rack (minimum
requirements)
● 64 outlets (for single phase PDU)
Note: 48 outlets (for three phase
PDUs) with two maximum PDUs
(115/208V 30A for US and
230/400V 16A for EU).
● Horizontal mount
Heat dissipation
● Pillar Axiom 600 systems:
28,500BTU/hr
● Pillar Axiom 600 systems:
28,500BTU/hr
Frame thickness
N/A
12 gauge to 14 gauge
Loaded weight
● Pillar Axiom 600 systems: 1505
pounds (683 kilograms)
● Pillar Axiom 600 systems:
1505 pounds (683 kilograms)
The center of gravity of a populated Pillar 42U rack is toward the front. The
threshold tilt angle depends on whether the front or back of the rack faces down
the slope:
● Front faces downward: 12° maximum slope.
● Back faces downward: 24° maximum slope.
Figure 68 Maximum tilt angles for stationary Pillar 42U racks
Appendix C Pillar Axiom Hardware Specifications
Pillar Rack Hardware Specification
203