86
41014 – 41015
Reserved
41016
Return time of relay 1
R/W
0 –1200s
0 means blocking.
41017
Return time of relay 2
R/W
0 – 1200s
0 means blocking.
41018
Return time of relay 3
R/W
0 – 1200s
0 means blocking.
41019
Return time of relay 4
R/W
0 – 1200s
0 means blocking.
41020 – 41021
Reserved
41022
Active energy pulse output
R/W
0 – Off
1 – Active energy input
2 – Active energy output
41023
Reactive energy pulse
output
R/W
0 – Off
1 – Reactive energy input
2 – Reactive energy output
41024
Pulse output constant
R/W
220 V/5 A, range:
1000 – 5000
100 V/5 A, 220 V/1 A,
range:
1000 – 20000
100 V/1 A, range:
1000 – 40000
The step length is 100.