Function description
Operating Manual PSSu K F EI
1003303-EN-03
| 27
4.5.5.2
Reaction on SS1-M (c)
}
The ST output O00 is shut down immediately.
}
The FS outputs are shut down after a configured delay time (STO delay time) has
elapsed. The delay time starts running with a 1/0 pulse edge at the signal for the restart
interlock or at the signal for the FS-O data types.
– If the delay time has elapsed and the signal for the restart interlock or FS-O data
types is "0", then the assigned output is set to "0".
– If the delay time has elapsed and the signal for the restart interlock or FS-O data
types is "1", then the assigned output remains at "1".
– If the delay time is running and another 1/0 pulse edge arrives at the signal for the re-
start interlock or FS-O data types, then the delay time is restarted.
0
1
0
1
0
1
1
0
1
0
0
1
0
1
0
1
0
O00
ST_O_DO
FS_O_DO
FS_O_DO
1
O01
O02
Restart interlock
Outputs shut down
via the monitoring
functions
Outputs shut down
via an
O-data type
O00 STO
delay time
O01 STO
delay time
Legend
:
}
Restart interlock
}
ST_O_DO: O-data type for the ST output
}
FS_O_DO: O-data type for the FS output
}
O00: ST output
}
STO delay time: Delay time for shutting down the FS outputs
}
O01: FS output that can be used to trigger the STO function on a connected drive.
}
O02: FS output that can be used to trigger the STO function on a connected drive.