Wiring
Operating Manual PSSu K F EI
1003303-EN-03
| 51
– Hiperface (A,/A,B,/B) + HTL single ended (A as Z)
Please note:
Track /Z must remain free
Encoder
Mini-IO
6.7
EMC-compliant wiring
EMC-compliant wiring for connecting an encoder
Encoder
U
B
X31
To avoid EMC interference we recommend that the shield on the sensor lines is only con-
nected to earth at a single point:
A
or
B
Conductor loops outside the shield must be avoided.
The shield must run continuously from the sensor to the evaluation device.