Operation
Operating Manual PSSu K F EI
1003303-EN-03
| 54
7
Operation
7.1
Messages
A module error is displayed via the "Err" LED, signalled to the head module and then
entered in the head module's diagnostic log.
The module can detect the following errors:
Module error
Statement
Remedy
Start-up error
Error as the PSSu system
starts up
Change faulty module.
Configuration error
Incorrect module type con-
figured.
The configured hardware re-
gistry does not match the ac-
tual hardware registry.
FS communication error
Error during FS communica-
tion
Change faulty module.
Bus termination error
There is no terminating plate
or there is a bad contact with
the module bus.
Install a terminating plate
with integrated end bracket
or insert the base modules
together correctly.
Temperature error: too warm Ambient temperature too
high:
Error stack entry/diagnostic
log entry
Ensure there is sufficient
ventilation in the control cab-
inet or prevent overload.
Output error
Error during cyclical output
test for short circuit. Possible
causes: Short circuit, or out-
put defective.
Rectify the short circuit or
change the faulty module.
Encoder error
No encoder connected
The encoder must be con-
nected correctly
Parameter error
Incorrect parameter
(Max_Speed or Min_Speed)
Change the parameter