Operating Manual PNOZ s3 
21395-EN-10

6

}

  Calculation of the max. cable length l

max

 in the input circuit:

  

  R

lmax

 = max. overall cable resistance (see technical details) 

R

l

 / km = cable resistance/km

}

  Use copper wire that can withstand 60/75 °C.

}

  Sufficient fuse protection must be provided on all output contacts with capacitive and in-

ductive loads.

}

  When connecting magnetically operated, reed proximity switches, ensure that the max. 

peak inrush current (on the input circuit) does not overload the proximity switch.

Preparing for operation

Operating modes

The operating mode is set via the rotary switch on the unit. You can do this by opening the 
cover on the front of the unit.

CAUTION!

Do not adjust the rotary switch during operation, otherwise an error mes-
sage will appear, the safety contacts will open and the unit will not be ready 
for operation until the supply voltage has been switched off and then on 
again.

Set operating modes

}

  Switch off supply voltage.

}

  Select operating mode via the operating mode selector switch "mode".

}

  If the operating mode selector switch "mode" is in its start position (vertical position), an 

error message will appear.

Operating mode 

selector switch 

"mode"

Automatic/man-

ual start

Monitored start 

rising edge

Monitored start 

falling edge

Automatic start 

with start-up test

Without detec-

tion of shorts 

across contacts

 

 

 

 

With detection of 

shorts across 

contacts

 

 

 

 

Summary of Contents for 750103

Page 1: ...PNOZ s3 Operating Manual 21395 EN 10 Safety relays...

Page 2: ...es may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the s...

Page 3: ...prevention Ensure VDE and local regulations are met especially those relating to safety Any guarantee is rendered invalid if the housing is opened or unauthorised modifica tions are carried out Unit...

Page 4: ...the relay contacts Basic insulation overvolt age category III safe separation overvoltage category II Function description Single channel operation no redundancy in the input circuit earth faults in t...

Page 5: ...r module Installation Install base unit without contact expansion module Ensure that the plug terminator is inserted at the side of the unit Connect base unit and PNOZsigma contact expansion module Re...

Page 6: ...switch on the unit You can do this by opening the cover on the front of the unit CAUTION Do not adjust the rotary switch during operation otherwise an error mes sage will appear the safety contacts wi...

Page 7: ...channel Dual channel Emergency stop without detection of shorts across contacts Emergency stop with detection of shorts across contacts Safety gate without detection of shorts across contacts Safety g...

Page 8: ...on when the Power LED is permanently lit LEDs indicate the status and errors during operation LED on LED flashes Information Status indicators and error indicators may occur independently In the case...

Page 9: ...hed off Remedy Rectify short across contacts earth fault switch off supply voltage for 1 min Fault Diagnostics Plug terminator not connected Remedy Insert plug terminator switch supply voltage off and...

Page 10: ...rcuits S12 and S22 simultaneously and then close again Reset Fault Diagnostics Position of rotary switch is not permitted or rotary switch was ad justed during operation Remedy Switch supply voltage o...

Page 11: ...ible Example Inductive load 0 2 A Utilisation category AC15 Contact service life 2 000 000 cycles Provided the application requires fewer than 2 000 000 cycles the PFH value see techni cal details can...

Page 12: ...0 20 A 0 20 A Max overall cable resistance Rl max Single channel at UB DC 30 Ohm 30 Ohm Dual channel without detection of shorts across contacts at UB DC 60 Ohm 60 Ohm Dual channel with detection of s...

Page 13: ...current 5 0 A 5 0 A Contact fuse protection external safety contacts In accordance with the standard EN 60947 5 1 EN 60947 5 1 Blow out fuse quick 10 A 10 A Blow out fuse slow 6 A 6 A Circuit breaker...

Page 14: ...e de ener gisation 20 ms 20 ms Simultaneity channel 1 and 2 Environmental data 750103 751103 Climatic suitability EN 60068 2 78 EN 60068 2 78 Ambient temperature Temperature range 10 55 C 10 55 C Stor...

Page 15: ...rew terminal Spring loaded terminal Mounting type plug in plug in Cross section of external conduc tors with spring loaded terminals flexible with without crimp connec tor 0 20 2 50 mm 24 12 AWG Sprin...

Page 16: ...ervice life graphs are not accessible the stated PFH value can be used irrespective of the switching frequency and the load as the PFH value already considers the relay s B10d val ue as well as the fa...

Page 17: ...raNET p Pilz PIT PMCprotego PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would po...

Reviews: