Safety Regulations

• The unit may only be installed and

operated by personnel who are familiar
with both these instructions and the
current regulations for safety at work and
accident prevention. Follow VDE and
local regulations especially as regards
preventative measures.

• Transport, storage and operating

conditions should all conform to
EN 60068-2-6.

• Any guarantee is void following opening of

the housing or unauthorised
modifications.

• The unit should be panel mounted,

otherwise dampness or dust could lead to
function impairment.

• Adequate protection must be provided on

all output contacts especially with
capacitive and inductive loads.

Sicherheitsbestimmungen

• Das Gerät darf nur von Personen

installiert und in Betrieb genommen
werden, die mit dieser Betriebsanleitung
und den geltenden Vorschriften über
Arbeitssicherheit und Unfallverhütung
vertraut sind. Beachten Sie die VDE-
sowie die örtlichen Vorschriften, insbe-
sondere hinsichtlich Schutzmaßnahmen.

• Beim Transport, der Lagerung und im

Betrieb die Bedingungen nach EN 60068-
2-6 einhalten (s. technische Daten).

• Durch Öffnen des Gehäuses oder eigen-

mächtige Umbauten erlischt jegliche Ge-
währleistung.

• Montieren Sie das Gerät in einen

Schaltschrank; Staub und Feuchtigkeit
können sonst zu Beeinträchtigungen der
Funktionen führen.

• Sorgen Sie an allen Ausgangskontakten

bei kapazitiven und induktiven Lasten für
eine ausreichende Schutzbeschaltung.

Conseils préliminaires

• La mise en oeuvre de l’appareil doit être

effectuée par une personne spécialisée
en installations électriques, en tenant
compte des prescriptions des différentes
normes applicables (NF, EN, VDE...)
notamment au niveau des risques
encourus en cas de défaillance de
l’équipement électrique.

• Respecter les exigences de la norme

EN 60068-2-6 lors du transport, du
stockage et de l'utilisation de l'appareil.

• L’ouverture de l’appareil ou sa modifi-

cation annule automatiquement la
garantie.

• L’appareil doit être monté dans une ar-

moire; l’humidité et la poussière pouvant
entraîner des aléas de fonctionnement.

• Vérifiez que le pouvoir de coupure des

contacts de sortie est suffisant en cas de
circuits capacitifs ou inductifs.

Bestimmungsgemäße Verwen-
dung

Das Sicherheitsschaltgerät dient dem
sicherheitsgerichteten Unterbrechen eines
Sicherheitsstromkreises.
Das Sicherheitsschaltgerät erfüllt Forderun-
gen der EN 60947-5-1, EN 60204-1 und
VDE 0113-1 und darf eingesetzt werden in
Anwendungen mit
• Not-Halt-Tastern
• Schutztüren

Das Gerät ist nicht für die Absicherung von
berührungslosen Verdeckungen geeignet, da
kein dynamischer Start möglich ist.

Gerätebeschreibung

Das Sicherheitsschaltgerät PNOZ X2/X2.1/
X2.2 ist in einem S-95-Gehäuse unterge-
bracht. Es kann mit 24 V Wechselspannung
oder mit 24 V Gleichspannung betrieben
werden.
Merkmale:
• Relaisausgänge: 2 Sicherheitskontakte

(Schließer), zwangsgeführt

• Anschlussmöglichkeit für Not-Halt-

Taster, Schutztürgrenztaster und
Starttaster

• PNOZ X2: überwachter Starttaster
• PNOZ X2.1: automatischer Start möglich
• PNOZ X2.2: wie PNOZ X2, zusätzlich

können mehrere Geräte parallel mit einem
Starttaster gestartet werden

• Statusanzeige
• Überwachung externer Schütze möglich
• keine galvanische Trennung

Das Schaltgerät erfüllt folgende Sicherheits-
anforderungen:
• Schaltung ist redundant mit Selbst-

überwachung aufgebaut

Domaines d’utilisation

Le bloc logique de sécurité sert à
interrompre en toute sécurité un circuit de
sécurité.
Le bloc logique de sécurité satisfait aux
exigences des normes EN 60947-5-1,
EN 60204-1 et VDE 0113-1 et peut être
utilisé dans des applications avec des
• poussoirs d’arrêt d’urgence
• protecteurs mobiles

L'appareil n'est pas adapté à la surveillance
de barrières immatérielles car une validation
dynamique n'est pas possible (surveillance
du circuit de réarmement).

Description de l’appareil

Inséré dans un boîtier S 95, le bloc logique
de sécurité PNOZ X2/X2.1/X2.2 peut être
alimenté en 24 V AC ou en 24 V DC.
Particularités :
• Sorties disponibles : 2 contacts à

fermeture de sécurité

• Bornes de raccordement pour poussoirs

AU, détecteurs de position et poussoir de
validation

• PNOZ X2: surveillance du circuit de

validation

• PNOZ X2.1: réarmement automatique

possible

• PNOZ X2.2: comme PNOZ X2, mais

permet le réarmement de plusieurs
appareils en parallèle avec un seul
poussoir de réarmement.

• LEDs de visualisation
• Auto-contrôle des contacteurs externes

possible

• pas d'isolation galvanique

Le relais PNOZ X2/X2.1/X2.2 répond aux
exigences suivantes :
• conception redondante avec auto-

surveillance

Authorised Applications

The safety relay provides a safety-related
interruption of a safety circuit.
The safety relay meets the requirements of
EN 60947-5-1, EN 60204-1 and VDE 0113-
1 and may be used in applications with
• E-STOP pushbuttons
• Safety gates

The device is not suitable for non-contact
barriers (e.g. light curtains) because a
dynamic start is not possible.

Description

The Safety Relay PNOZ X2/X2.1/X2.2 is
enclosed in a S-95 housing.  Every unit can
be operated with 24 V AC or 24 V DC.

Features:
• Relay outputs:  2 safety contacts (N/O),

positive-guided.

• Connections for Emergency Stop Button,

Safety Gate Limit Switch and Reset
button.

• PNOZ X2: monitored manual reset
• PNOZ X2.1: automatic reset possible
• PNOZ X2.2: As PNOZ X2. In addition,

several units may be started in parallel
using one start button.

• Status Indicators.
• Feedback Control Loop for monitoring of

external contactors/relays possible

• no galvanic seperation

The relay complies with the following safety
requirements:
• The circuit is redundant with built-in self-

monitoring

19238-6NL-04

PNOZ X2, PNOZ X2.1, PNOZ X2.2

4

D

Betriebsanleitung

4

GB Operating instructions

4

F

Manuel d'utilisation

4

E

Instrucciones de uso

4

I

Istruzioni per l`uso

4

NL Gebruiksaanwijzing

Summary of Contents for 774 303

Page 1: ...en werden Merkmale Relaisausg nge 2 Sicherheitskontakte Schlie er zwangsgef hrt Anschlussm glichkeit f r Not Halt Taster Schutzt rgrenztaster und Starttaster PNOZ X2 berwachter Starttaster PNOZ X2 1 a...

Page 2: ...edundanz im Eingangskreis Erdschl sse im Startkreis werden erkannt Bei Erdschl s sen im Not Halt Kreis l st die Sicherung der Versorgungsspannung aus Zweikanaliger Betrieb Redundanter Ein gangskreis E...

Page 3: ...Rlmax Max Total cable resistance see technical details Rl km Cable resistance km As the function for detecting shorts across the inputs is not failsafe it is tested by Pilz during the final control c...

Page 4: ...externes Input circuit Single channel Connect N C contact from safety switch between the positive terminal L of the operating voltage and terminal A1 link S11 S12 and S21 S22 Two channel Connect N C...

Page 5: ...Einschaltmoment Sicherheitstechnische Kenn daten der Sicherheitsausg nge PL nach EN ISO 13849 1 Kategorie nach EN 954 1 SIL CL nach EN IEC 62061 PFH nach EN IEC 62061 SIL nach IEC 61511 PFD nach IEC...

Page 6: ...rew Dimensions H x W x D Weight Temporisations Temps de r armement R armement automatique R armement manuel R armement manuel auto contr l Temps de retomb e en cas d arr t d urgence en cas de coupure...

Page 7: ...lz com Bevollm chtigter Norbert Fr hlich Pilz GmbH Co KG Felix Wankel Str 2 73760 Ostfildern Deutschland EC Declaration of Conformity This these product s comply with the requirements of Directive 200...

Page 8: ...tte unserer Homepage oder nehmen Sie Kontakt mit unserem Stammhaus auf Nos filiales et partenaires commerciaux nous repr sentent dans plusieurs pays Pour plus de renseignements consultez notre site in...

Page 9: ...deguata protezione per tutti i contatti di uscita Uso previsto Il modulo di sicurezza consente l interruzione sicura di un circuito di sicurezza Il modulo di sicurezza risponde ai requisiti secondo EN...

Page 10: ...K2 tornano nella posizione di riposo La visualizzazione stato per CH 1 e CH 2 si spegne I contatti di sicurezza 13 14 23 24 si aprono in modo ridondante Modalit operative Funzionamento monocanale Cab...

Page 11: ...h la funzione di rilevamento cortocircuito non protetta dagli errori essa viene controllata dalla Pilz durante il collaudo finale Una verifica dopo l installa zione dell apparecchio pu essere eseguita...

Page 12: ...laars entre las conexiones S33 y S34 Todos los dispositivos se deben conectar a la misma alimentaci n de tensi n Circuitos de entrada Monocanal Conectar el contacto NC del elemento de activaci n entre...

Page 13: ...ircuitos de entrada circuito de rearme monocanal DC monocanal AC bicanal con detecci n de derivacion DC bicanal con detecci n de derivacion AC Resistencia de entrada m n en el instante de la conexi n...

Page 14: ...a vite 1 conduttore flessibile 2 conduttori con lo stesso diametro flessibile con capocorda senza manicotto di plastica flessibile senza capocorda o con capocorda TWIN Coppia di serraggio per morsett...

Page 15: ...conformidad completa pueden encontrarla en la p gina web de Internet www pilz com Apoderado Norbert Fr hlich Pilz GmbH Co KG Felix Wankel Str 2 73760 Ostfildern Deutschland Dichiarazione di conformit...

Page 16: ...lspartners Voor meer informatie kunt u onze homepage raadplegen of contact opnemen met ons hoofdkantoor In molti Paesi siamo rappresentati da partner commerciali Per maggiori informazioni potete conta...

Reviews: