PNOZ X3.1
Operating Manual PNOZ X3.1
20133-EN-06
18
Times
774321
774322
Switch-on delay
With automatic start typ.
250 ms
250 ms
With automatic start max.
500 ms
500 ms
With automatic start after power
on typ.
280 ms
280 ms
With automatic start after power
on max.
550 ms
550 ms
With monitored start typ.
35 ms
35 ms
With monitored start max.
50 ms
50 ms
Delay-on de-energisation
With E-STOP typ.
15 ms
15 ms
With E-STOP max.
30 ms
30 ms
With power failure typ.
50 ms
50 ms
With power failure max.
70 ms
70 ms
Recovery time at max. switching
frequency 1/s
After E-STOP
50 ms
50 ms
After power failure
100 ms
100 ms
Waiting period with a monitored
start
300 ms
300 ms
Min. start pulse duration with a
monitored start
30 ms
30 ms
Supply interruption before de-ener-
gisation
20 ms
20 ms
Simultaneity, channel 1 and 2 max.
∞
∞
Environmental data
774321
774322
Climatic suitability
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-20 - 55 °C
-20 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C
Climatic suitability
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during operation
Not permitted
Not permitted
EMC
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
Vibration
In accordance with the standard
EN 60068-2-6
EN 60068-2-6
Frequency
10 - 55 Hz
10 - 55 Hz
Amplitude
0,35 mm
0,35 mm
Airgap creepage
In accordance with the standard
EN 60947-1
EN 60947-1
Overvoltage category
III / II
III / II
Pollution degree
2
2
Rated insulation voltage
250 V
250 V
Rated impulse withstand voltage
4 kV
4 kV