PNOZ X10.11P
Operating Manual PNOZ X10.11P
20820-EN-13
| 17
Relay outputs
777750
787750
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Max. melting integral
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
Blow-out fuse, slow
6 A
6 A
Blow-out fuse, gG
10 A
10 A
Circuit breaker 24V AC/DC,
characteristic B/C
6 A
6 A
External contact fuse protection,
auxiliary contacts
Max. melting integral
240 A²s
240 A²s
Blow-out fuse, quick
10 A
10 A
Blow-out fuse, slow
6 A
6 A
Blow-out fuse, gG
10 A
10 A
Circuit breaker 24 V AC/DC,
characteristic B/C
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
Conventional thermal current
while loading several contacts
777750
787750
Ith per contact at UB DC;
AC1: 240 V, DC1: 24 V
Conv. therm. current with 1 con-
tact
8 A
8 A
Conv. therm. current with 2 con-
tacts
8 A
8 A
Conv. therm. current with 3 con-
tacts
8 A
8 A
Conv. therm. current with 4 con-
tacts
7 A
7 A
Conv. therm. current with 5 con-
tacts
6 A
6 A
Conv. therm. current with 6 con-
tacts
5,5 A
5,5 A
Times
777750
787750
Switch-on delay
With automatic start typ.
200 ms
200 ms
With automatic start max.
250 ms
250 ms
With automatic start after power
on typ.
220 ms
220 ms
With automatic start after power
on max.
300 ms
300 ms
With manual start typ.
200 ms
200 ms
With manual start max.
250 ms
250 ms
With monitored start typ.
220 ms
220 ms
With monitored start max.
260 ms
260 ms