P2HZ X4P
Operating Manual P2HZ X4P
20076-EN-08
10
}
t
0
: Recovery time after power on
}
t
1
: Simultaneity, channel 1 and 2
}
t
2
: Operating cycle ended through pushbutton 1 or 2
}
t
3
: Y1-Y2 must be closed before the button is operated (recovery time)
Shaded area: State irrelevant
Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}
When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle).
}
Fit the input terminal block of the control cabined with additional terminals for the supply
voltage.
WARNING!
Loss of the safety function due to too short distance of the operator
elements to the hazardous area!
The distance of the two-hand control relay to the nearest hazardous area
must be large enough so that if one of the operator elements is released,
the hazardous movement is interrupted before the operator reaches the
hazardous area or can reach into the hazardous area. You must maintain
the minimum distance in accordance with EN ISO 13855.
Depending on the application, serious injury or death may result.