4.5
Installing the Dynamic Energy Storage Unit
Basic information
• The Dynamic Energy Storage Unit is intended to be installed in an electrical cabinet.
• The Dynamic Energy Storage Unit must be protected against foreign bodies from
falling in through the cabinet.
• The unit is installed directly on a mounting surface in the switch cabinet.
• The Dynamic Energy Storage Unit needs to be installed right next to the applica
-
tion (frequency converter, servo controller) due to the length of the connecting
cable (max. 1 m).
Spacing
During installation, the following spacings to other modules must be maintained:
• at the side: at least 20 mm.
• above and below: at least 100 mm.
Installation
Fig. 4: Drilling template
⌧
Install the Dynamic Energy Storage Unit according to the drilling template,
vertically, using four bolts (M6).
The power connection is at the bottom.
⌧
Check that it is firmly seated.
There is a risk of damage.
The Dynamic Energy Storage Unit must not be mounted upside
down.
⌧
Install the Dynamic Energy Storage Unit vertically.