Installation
Operating Manual PMI 6
1003280-EN-01
17
5.3
Installing the unit
When installing the device, please note the following:
}
For reasons of stability, the front panel, console or control cabinet should have a wall
thickness of at least 2.5 mm.
}
To avoid the accumulation of heat, a distance of 10 cm/3.94" should be maintained
around the device.
}
Ensure the information given for the ambient and operating temperatures in the tech-
nical details is observed.
}
IP65 protection can only be guaranteed when
– the device's fixing screws are tightened with the following torque: min. 0.2 Nm, max.
0.4 Nm.
– the gasket is not damaged.
– the wall thickness is at least 2.5 mm.
5.4
Installation
Fig.: Installing the PMI 607 Control
Fig.: Installing the PMI 612 Control