PNOZ 15
Operating Manual PNOZ 15
18492-EN-04
14
Faults – Interference
}
Earth fault/short circuit
An internal fuse interrupts the supply voltage, the safety contacts are opened and the
"FAULT" LED is lit. Once the cause of the fault has been removed, press the reset but-
ton to reset the fuse.
}
Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.
}
LED "POWER" does not light: Short circuit or no supply voltage.
Dimensions in mm
121 (4.76")
75 (2.95")
87 (3.42")
90 (3.54")
Technical details
General
Approvals
CCC, CE, TÜV
Electrical data
Supply voltage
Voltage
24 V
Kind
DC
Voltage tolerance
-15 %/+10 %
Output of external power supply (DC)
3,5 W
Residual ripple DC
160 %
Duty cycle
100 %
Max. inrush current impulse
Current pulse, A1
11 A
Pulse duration, A1
15 ms
Inputs
Number
2