PNOZ 15
Operating Manual PNOZ 15
18492-EN-04
15
Inputs
Voltage at
Input circuit DC
24 V
Start circuit DC
24 V
Feedback loop DC
24 V
Current at
Input circuit DC
50 mA
Start circuit DC
50 mA
Feedback loop DC
50 mA
Max. inrush current impulse
Current pulse, start circuit
0,95 A
Pulse duration, start circuit
15 ms
Max. overall cable resistance Rlmax
Single-channel at UB DC
100 Ohm
Dual-channel without detection of shorts across
contacts at UB DC
200 Ohm
Dual-channel with detection of shorts across con-
tacts at UB DC
5 Ohm
Semiconductor outputs
Number
1
Voltage
24 V
Current
50 mA
External supply voltage
24 V
Voltage tolerance
-30 %/+30 %
Short circuit-proof
yes
Relay outputs
Number of output contacts
Safety contacts (N/O), instantaneous
3
Auxiliary contacts (N/C)
1
Auxiliary contacts (N/O)
1
Max. short circuit current IK
1 kA
Utilisation category
In accordance with the standard
EN 60947-4-1
Utilisation category of safety contacts
AC1 at
400 V
Min. current
0,01 A
Max. current
5 A
Max. power
2000 VA
AC1 at
240 V
Min. current
0,01 A
Max. current
8 A
Max. power
2000 VA
DC1 at
24 V
Min. current
0,01 A
Max. current
8 A
Max. power
200 W