PNOZ 15
Operating Manual PNOZ 15
18492-EN-04
16
Relay outputs
Utilisation category of auxiliary contacts
AC1 at
240 V
Min. current
0,01 A
Max. current
5 A
Max. power
1200 VA
DC1 at
24 V
Min. current
0,01 A
Max. current
5 A
Max. power
120 W
Utilisation category
In accordance with the standard
EN 60947-5-1
Utilisation category of safety contacts
AC15 at
230 V
Max. current
5 A
DC13 (6 cycles/min) at
24 V
Max. current
7 A
Utilisation category of auxiliary contacts
AC15 at
230 V
Max. current
2 A
DC13 (6 cycles/min) at
24 V
Max. current
2 A
External contact fuse protection, safety contacts
In accordance with the standard
EN 60947-5-1
Max. melting integral
240 A²s
Blow-out fuse, quick
10 A
Blow-out fuse, slow
6 A
Blow-out fuse, gG
10 A
Circuit breaker 24V AC/DC, characteristic B/C
6 A
External contact fuse protection, auxiliary contacts
Max. melting integral
240 A²s
Blow-out fuse, quick
6 A
Blow-out fuse, slow
4 A
Blow-out fuse, gG
6 A
Circuit breaker 24 V AC/DC, characteristic B/C
4 A
Conventional thermal current
8 A
Contact material
0,2 µm Au
Times
Switch-on delay
Typ. switch-on delay
450 ms
Max. switch-on delay
900 ms
Delay-on de-energisation
With E-STOP typ.
15 ms
With E-STOP max.
50 ms
With power failure typ.
100 ms
With power failure max.
200 ms