PNOZ c2

Operating Manual PNOZ c2
22212­EN­02

6

Safety features

The relay meets the following safety requirements:

}

The circuit is redundant with built­in self­monitoring.

}

The safety function remains effective in the case of a component failure.

}

The correct opening and closing of the safety function relays is tested automatically in
each on­off cycle.

Block diagram/terminal configuration

*Insulation to the non­marked area: Protective separation (overvoltage category III), 
Insulation of relay contacts against each other: Basic insulation (overvoltage category III),
protective separation (overvoltage category II)

Function description

When the supply voltage is supplied, the "POWER" LED illuminates. The unit is ready for
operation when the start circuit is closed or when a start contact is opened and closed
again in the start circuit.

}

High signal at input circuit (e.g. light guard nor interrupted): The safety contacts are
closed and the semiconductor output transmits.

}

Low signal at the input circuit (e.g. light guard is interrupted): The safety contacts are
open and the semiconductor output is de­energised.

}

Dual­channel operation without detection of shorts across contacts: redundant input cir­
cuit, detects earth faults in the start and input circuit.

}

Automatic start: Unit becomes active as soon a there is a high signal at the input circuit.

}

Monitored start: Unit is active once there is a high signal at the input circuit and then the
start circuit is closed.

}

Increase in the number of available instantaneous safety contacts by connecting con­
tact expander modules or external contactors.

Summary of Contents for PNOZ c2

Page 1: ...PNOZ c2 Operating Manual 22212 EN 02 Safety relays...

Page 2: ...KG Copies may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET...

Page 3: ...r your safety 5 Unit features 5 Safety features 6 Block diagram terminal configuration 6 Function description 6 Installation 7 Wiring 7 Preparing for operation 7 Operation 9 Status indicators 9 Faults...

Page 4: ...This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken WARNING This warning must b...

Page 5: ...with the documented technical details For your safety Only install and commission the unit if you have read and understood these operating instructions and are familiar with the applicable regulation...

Page 6: ...The unit is ready for operation when the start circuit is closed or when a start contact is opened and closed again in the start circuit High signal at input circuit e g light guard nor interrupted Th...

Page 7: ...welding a fuse should be connected before the output contacts see Technical details Use copper wire that can withstand 60 75 C Do not connect capacitive load The power supply must comply with the reg...

Page 8: ...ht guard Use the free connections A1 and A2 for connecting the supply voltage of the sender Start circuit feedback loop Start circuit Feedback loop automatic start monitored start NOTICE The unit auto...

Page 9: ...ircuit has opened Technical details General 710002 Approvals CCC CE EAC Eurasian T V cULus Listed Electrical data 710002 Supply voltage Voltage 24 V Kind DC Voltage tolerance 20 20 Output of external...

Page 10: ...contacts DC 1 at 24 V Max current 4 0 A Min current 0 01 A Max power 100 W Utilisation category In accordance with the standard EN 60947 5 1 Safety contacts AC15 at 230 V Max current 1 5 A Safety con...

Page 11: ...0 ms Simultaneity channel 1 and 2 Environmental data 710002 Climatic suitability EN 60068 2 78 Ambient temperature Temperature range 10 55 C Storage temperature Temperature range 40 85 C EMC EN 60947...

Page 12: ...62061 SIL CL EN IEC 62061 PFHD 1 h IEC 61511 SIL IEC 61511 PFD EN ISO 13849 1 2008 TM year Safety con tacts in stantaneous PL e Cat 4 SIL CL 3 2 31E 09 SIL 3 2 03E 06 20 INFORMATION All the units use...

Page 13: ...on the relay output If the service life graphs are not accessible the stated PFH value can be used irrespective of the switching frequency and the load as the PFH value already considers the relay s B...

Page 14: ...must be provided on all output contacts With DC contactors use flywheel diodes for spark suppression Order reference Type Features Terminals Order no PNOZ c2 24 VDC With spring loaded terminals 710 0...