Commissioning
Operating Manual PNOZ m EF 8DI2DOT
1004649-EN-03
| 17
6
Commissioning
6.1
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Please note:
}
Information given in the
Technical details [
22]
must be followed.
}
The position of the expansion module is specified in the Hardware configuration of the
PNOZmulti Configurator.
}
Use copper wiring with a temperature stability of 75 °C.
}
Protect the supply voltage as follows:
– Circuit breaker, characteristic C - 6 A
or
– Blow-out fuse, slow, 6 A
}
The unit has two dual-pole semiconductor outputs. These may be configured as single-
pole or redundant outputs. The output assignment is defined in the PNOZmulti Configur-
ator. Wire the outputs as described in the table.
NOTICE
Please note:
Loads over 10 kOhm may mistakenly be detected as an open circuit.
Open circuit detection can be configured and also deactivated in PNOZmulti
Configurator.