PNOZ m ES Profibus
Operating Manual PNOZ m ES Profibus
1002698EN04
10
The outputs are configured in the PNOZmulti Configurator and transferred to the
Master.
}
Status of LEDs:
–
Bits 0 … 4: Status of LEDs on the PNOZmulti 2
Bit 0: OFAULT
Bit 1: IFAULT
Bit 2: FAULT
Bit 3: DIAG
Bit 4: RUN
}
Data exchange is displayed in Bit 5.
}
Polling the usable data: 2 Bytes with the table number and segment number are sent by
the Master for access to the usable data table (15 Bytes are returned to the Master).
Detailed information on data exchange (tables, segments) is available in the document
"Communication Interfaces" in the section entitled "Fieldbus modules".
Assigning the inputs/outputs in the PNOZmulti Configurator to the PROFIBUSDP
inputs/outputs
Virtual inputs and outputs can be requested or set directly via the following objects. Each
element can be selected individually in the master control system, e.g. virtual inputs i031.
The data width is also established this way.
Input data
The Master writes to the virtual inputs of the PNOZmulti 2.
Description
Input data from PNOZmulti 2
Virtual inputs i0 – i31
4 Input Bytes
Virtual inputs i32 – i63
4 Input Bytes
Virtual inputs i64 – i95
4 Input Bytes
Virtual inputs i96 – i127
4 Input Bytes
Output data
The Master reads the virtual outputs of the PNOZmulti 2.
Description
Output data from PNOZmulti 2
Virtual outputs o0 – o31
4 Output Bytes
Virtual outputs o32 – o63
4 Output Bytes
Virtual outputs o64 – o95
4 Output Bytes
Virtual outputs o96 – o127
4 Output Bytes