Function description
Operating Manual PNOZ m ES Profibus
1002698-EN-05
12
4.3
Assigning the inputs/outputs in the PNOZmulti Configurator
to the PROFIBUS-DP inputs/outputs
Virtual inputs and outputs can be requested or set directly via the following objects. Each
element can be selected individually in the master control system, e.g. virtual inputs i0-31.
The data width is also established this way.
Input data
The Master writes to the virtual inputs of the PNOZmulti 2.
Description
Input data from PNOZmulti 2
Virtual inputs i0 – i31
4 Input Bytes
Virtual inputs i32 – i63
4 Input Bytes
Virtual inputs i64 – i95
4 Input Bytes
Virtual inputs i96 – i127
4 Input Bytes
Output data
The Master reads the virtual outputs of the PNOZmulti 2.
Description
Output data from PNOZmulti 2
Virtual outputs o0 – o31
4 Output Bytes
Virtual outputs o32 – o63
4 Output Bytes
Virtual outputs o64 – o95
4 Output Bytes
Virtual outputs o96 – o127
4 Output Bytes
4.4
Block diagram
Base unit
PROFIBUS DP
24 V 0 V