Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
7-1
7.1
Messages
7
Operation
7
7000
Operation
Operation
7-
7.1
Messages
7100
Messages
7-
Betrieb_Meldungen_Basis_BA
The PNOZmulti safety system is ready for operation when the "POWER"
and "RUN" LEDs on the base unit are lit continuously.
7.1.1
Display elements for device diagnostics
Display elements for device diagnostics
7-
Anzeige Legende 3x
Key:
Betrieb_Anzeige_multi_Basis_ETH_BA
LED on
LED flashes
LED off
Basic
Exp.
Errors
Input Ix
RUN
DIAG
FAU
L
T
IFAULT
OFAULT
CI
CO
FAU
L
T
IN/OUT
The existing user program has been deleted.
External error on the base unit, leading to a safe condition, e.g.
terminator not connected.
External error, leading to a safe condition, e.g. short across the
contacts or error on safety mat input.
External error on the outputs of the base unit, e.g. short across
the contacts, leading to a safe condition.
External error, leading to a safe condition, e.g. short across the
contacts.
External error on the output
Internal error on the base unit
Internal error on the base unit
Internal error on the base unit
Internal error on the expansion module
Base unit in a STOP condition
External error on the inputs of the base unit, which does not
lead to a safe condition, e.g. partially operated.
External error on the outputs of the base unit, which does not
lead to a safe condition, e.g. feedback input defective.
External error on the inputs, which does not lead to a safe con-
dition, e.g. partially operated; feedback input defective.