8
Technical details
8.2
Service life graph of output relays
8200
Service life graph of output relays
8-
Lebensdauerkurve_Relais_Text vor Kurve
The service life graphs indicate the number of cycles from which failures
due to wear must be expected. The wear is mainly caused by the elec-
trical load; the mechanical load is negligible.
Lebensdauerkurve SIS_212
Lebensdauerkurve_Relais_Text nach Kurve_SIS212_SIR-SLR Bsp
Example
`
Inductive load: 0.2 A
`
Utilisation category: AC15
`
Contact service life: 1 000 000 cycles
Provided the application requires fewer than 1 000 000 cycles, the PFH
value (see technical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provid-
ed on all output contacts. With capacitive loads, any power surges that
occur must be noted. With contactors, use freewheel diodes for spark
suppression.
Lebensdauerkurve_Relais_Text nach Kurve-2_ Empfehlung Halbleiterausgänge
We recommend you use semiconductor outputs to switch 24 VDC
loads.
10
1
10
100
1000
10000
0.1
DC1: 24 V
AC1: 230 V
DC13: 24 V
AC15: 230 V
D
Nennbetriebstr
om (A)
GB
Nominal operating current (A)
F
Courant coupé (A)
E
Corriente nominal de ser
vicio (A)
I
Corrente di eser
cizio nominale (A)
NL
Nominale bedrijfsstr
oom (A)
D Schaltspielzahl x 10
3
GB Cycles x 10
3
F
Nombre de manuvres x 10
3
E
Número de ciclos x 10
3
I
Numero dei cicli di commutazione x 10
3
NL Aantal schakelingen x 10
3