Installation

Operating Manual PNOZ mc7p
1003050­EN­02

12

5

Installation

5.1

General installation guidelines

}

The control system should be installed in a control cabinet with a protection type of at
least IP54. Fit the control system to a horizontal mounting rail. The venting slots must
face upward and downward. Other mounting positions could destroy the control system.

}

Use the notches on the rear of the unit to attach it to a mounting rail. Connect the con­
trol system to the mounting rail in an upright position, so that the earthing springs on the
control system are pressed on to the mounting rail.

}

The ambient temperature of the PNOZmulti units in the control cabinet must not exceed
the figure stated in the technical details, otherwise air conditioning will be required.

}

To comply with EMC requirements, the mounting rail must have a low impedance con­
nection to the control cabinet housing.

CAUTION!

Damage due to electrostatic discharge!

Electrostatic discharge can damage components. Ensure against discharge
before touching the product, e.g. by touching an earthed, conductive sur­
face or by wearing an earthed armband.

5.2

Dimensions

94 (3.70")

22,5

(0.88")

1

14 (4.49")

5.3

Connecting the base unit and expansion modules

You can install a maximum of 1 PNOZ mc7p to the left of the base unit.

}

Do 

not

 connect a terminator to the last expansion module on the left­hand side.

}

Install the expansion module in the position in which it is configured in the PNOZmulti
Configurator.

Summary of Contents for PNOZ mc7p

Page 1: ...PNOZ mc7p Operating Manual 1003050 EN 02 Configurable Control System PNOZmulti...

Page 2: ...es may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the s...

Page 3: ...lity 9 3 3 3 Disposal 9 3 3 4 For your safety 9 Section 4 Function description 10 4 1 Functions 10 4 2 Input and output data 10 4 3 Block diagram 11 Section 5 Installation 12 5 1 General installation...

Page 4: ...particularly important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventiv...

Page 5: ...Introduction Operating Manual PNOZ mc7p 1003050 EN 02 5 INFORMATION This gives advice on applications and provides information on special fea tures...

Page 6: ...3 selected via rotary switch Station type Remote Device Occupied stations 2 24 virtual inputs and outputs on the control system PNOZmulti can be defined in the PNOZmulti Configurator for communication...

Page 7: ...Overview Operating Manual PNOZ mc7p 1003050 EN 02 7 Legend LED Run SD RD L Err...

Page 8: ...s of the base units that can be connected The configurable control system PNOZmulti is used for the safety related interruption of safety circuits and is designed for use in E STOP equipment Safety ci...

Page 9: ...liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the purpose for which it is intended Damage can be attributed to not having followed the gu...

Page 10: ...structured as follows Input area Inputs on PNOZmulti Configurator i00 i23 Input data CC Link RYn RY1n with n 0 F Example i23 RY17 s F L B C B A 9 8 7 6 5 4 3 2 1 0 RY0n i15 i14 i13 i12 i11 i10 i09 i08...

Page 11: ...Function description Operating Manual PNOZ mc7p 1003050 EN 02 11 4 3 Block diagram Base unit DA FG PE DB DG SLD CC Link...

Page 12: ...PNOZmulti units in the control cabinet must not exceed the figure stated in the technical details otherwise air conditioning will be required To comply with EMC requirements the mounting rail must hav...

Page 13: ...zardous voltages in the case of a fault The power supply must meet the regulations for extra low voltages with protective sep aration CAUTION Only connect and disconnect the expansion module when the...

Page 14: ...ed using the PNOZmulti Configurator Proceed as described in the operat ing instructions for the base unit NOTICE For the commissioning and after every program change you must check whether the safety...

Page 15: ...on is not available Status timeout No supply voltage at the fieldbus module PNOZ mc7p L Err Red Fault detected Wrong station address or transmission rate Flashes evenly setting has been changed during...

Page 16: ...anic isolation Yes Test voltage 500 V AC Times Supply interruption before de energisation 20 ms Environmental data Ambient temperature In accordance with the standard EN 60068 2 14 Temperature range 0...

Page 17: ...cabinet IP54 Housing IP20 Terminals IP20 Potential isolation Potential isolation between Fieldbus and module voltage Type of potential isolation Functional insulation Rated surge voltage 500 V Mechani...

Page 18: ...mc7p 1003050 EN 02 18 9 Order reference 9 1 Product Product type Features Order no PNOZ mc7p Fieldbus module CC Link 773 716 9 2 Accessories Product type Features Order no PNOZmulti bus terminator Ter...

Page 19: ...mo PMCprotego PMCtendo PMD PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET p the spirit of safety are registered and protected trademarks of Pilz GmbH Co KG in some countries We would poi...

Reviews: