Operation
Operating Manual PNOZ mmc6p
1002425-EN-03
19
7
Operation
When the supply voltage is switched on, the PNOZmulti safety system copies the configur-
ation from the chip card.
The LEDs “POWER”, “DIAG”, “FAULT”, “IFAULT” and “OFAULT” will light up on the base
unit.
The expansion module PNOZ mmc6p is configured and started automatically. The LEDs
“RUN” and “ERR” display the status of the PNOZ mmc6p on CANopen.
If the expansion module PNOZ mmc6p does not receive a configuration from the base unit
for a period of 30 s, the expansion module PNOZ mmc6p connects to CANopen and "RUN"
status is displayed on CANopen. The error message "External Error" is sent to the Master.
7.1
Messages
Legend
LED on
LED flashes
LED off
LED
Key
PWR
Supply voltage is present
Supply voltage is not present
RUN
PNOZ mmc6p In "Operational" status
1
PNOZ mmc6p In "Stopped" status
PNOZ mmc6p In "Pre-Operational" status
No supply voltage or module error detected
ERR
CAN controller is in "Bus off" status
1
Error threshold value has been reached, the CAN controller has re-
ceived too many error telegrams
2
Monitoring error, activation of master-slave monitoring error, e.g.
heartbeat monitoring
3
Error in "Synchronisation" operating status, a synchronisation tele-
gram, e.g. with simultaneous writing on several devices, did not occur
within the configured time
No error