background image

PNOZ s8

Operating Manual PNOZ s8
21400-EN-10

15

Environmental data

750108

751108

Climatic suitability

EN 60068-2-78

EN 60068-2-78

Ambient temperature

Temperature range

-10 - 55 °C

-10 - 55 °C

Storage temperature

Temperature range

-40 - 85 °C

-40 - 85 °C

Climatic suitability

Humidity

93 % r. h. at 40 °C

93 % r. h. at 40 °C

Condensation during operation

Not permitted

Not permitted

EMC

EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1

EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1

Vibration

In accordance with the standard

EN 60068-2-6

EN 60068-2-6

Frequency

10 - 55 Hz

10 - 55 Hz

Amplitude

0,35 mm

0,35 mm

Airgap creepage

In accordance with the standard

EN 60947-1

EN 60947-1

Overvoltage category

III / II

III / II

Pollution degree

2

2

Rated insulation voltage

250 V

250 V

Rated impulse withstand voltage

4 kV

4 kV

Protection type

Housing

IP40

IP40

Terminals

IP20

IP20

Mounting area (e.g. control cab-
inet)

IP54

IP54

Mechanical data

750108

751108

Mounting position

Any

Any

Mechanical life

5,000,000 cycles

5,000,000 cycles

Material

Bottom

PC

PC

Front

PC

PC

Top

PC

PC

Connection type

Screw terminal

Spring-loaded terminal

Mounting type

plug-in

plug-in

Conductor cross section with screw
terminals

1 core flexible

0,25 - 2,5 mm², 24 - 12 AWG

2 core with the same cross sec-
tion, flexible with crimp connect-
ors, no plastic sleeve

0,25 - 1 mm², 24 - 16 AWG

2 core with the same cross sec-
tion, flexible without crimp con-
nectors or with TWIN crimp con-
nectors

0,2 - 1,5 mm², 24 - 16 AWG

Torque setting with screw terminals

0,5 Nm

Summary of Contents for PNOZ s8

Page 1: ...PNOZ s8 Operating Manual 21400 EN 10 Safety relays...

Page 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Page 3: ...ranty and liability 7 Disposal 7 For your safety 7 Unit features 8 Safety features 8 Block diagram terminal configuration 8 Function description 9 Timing diagram 9 Installation 9 Wiring 10 Preparing f...

Page 4: ...Contents Operating Manual PNOZ s8 21400 EN 10 4 Remove plug in terminals 19 Order reference 19 EC declaration of conformity 19...

Page 5: ...y important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures t...

Page 6: ...the areas described in this manual Use of the product outside the technical details see Technical details 13 NOTICE EMC compliant electrical installation The product is designed for use in an industri...

Page 7: ...e generic and specialist standards applicable to the spe cific application Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the...

Page 8: ...ts the following safety requirements The unit monitors its own output contacts The safety function remains effective in the case of a component failure Earth fault in the feedback loop Detected depend...

Page 9: ...terminator is inserted at the side of the unit Connect base unit and PNOZsigma contact expansion module Remove the plug terminator at the side of the base unit and at the contact expander module Conn...

Page 10: ...chnical details 13 Rl km cable resistance km Use copper wire that can withstand 60 75 C Sufficient fuse protection must be provided on all output contacts with capacitive and in ductive loads Ensure t...

Page 11: ...the mechanical contact on the relay cannot be tested automatically Depending on the operational environment measures to detect the non opening of switching elements may be required under some circums...

Page 12: ...indicators FAULT Diagnostics Internal error unit defective Remedy Switch supply voltage off and then on again change unit if neces sary Faults malfunctions Contact malfunctions If the contacts have w...

Page 13: ...750108 751108 Number 1 1 Voltage at Input circuit DC 24 V 24 V Current at Input circuit DC 65 mA 65 mA Max inrush current impulse Current pulse input circuit 0 6 A 0 6 A Pulse duration input circuit...

Page 14: ...h UL Voltage 240 V AC G P 240 V AC G P With current 3 A 3 A Voltage 24 V DC G P 24 V DC G P With current 3 A 3 A Pilot Duty B300 R300 B300 R300 External contact fuse protection safety contacts In acco...

Page 15: ...947 1 EN 60947 1 Overvoltage category III II III II Pollution degree 2 2 Rated insulation voltage 250 V 250 V Rated impulse withstand voltage 4 kV 4 kV Protection type Housing IP40 IP40 Terminals IP20...

Page 16: ...comply with the safety related characteristic data in order to achieve the required safety level for your plant machine Operating Mode EN ISO 13849 1 2015 PL EN ISO 13849 1 2015 Category EN 62061 SIL...

Page 17: ...in the service life table are not accessible the stated PFH value can be used irrespective of the switching frequency and the load as the PFH value already considers the relay s B10d value as well as...

Page 18: ...e category Max rated impulse withstand voltage 3000 m 150 V II 2 5 kV 100 V III 2 5 kV 4000 m 150 V II 2 5 kV 100 V III 2 5 kV 5000 m 100 V II 1 5 kV 24 V III 0 8 kV Reduction of rated insulation volt...

Page 19: ...nection type Order No PNOZ s8 24 VDC Screw terminals 750 108 PNOZ s8 C 24 VDC Spring loaded terminals 751 108 EC declaration of conformity This product these products meet the requirements of the dire...

Page 20: ...yNET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document depe...

Reviews: