PNOZ s8
Operating Manual PNOZ s8
21400-EN-10
9
Function description
with PNOZsigma base unit:
}
Dual-channel operation via PNOZsigma connector
without PNOZsigma base unit:
}
Single-channel operation: one input circuit affects the output relays
Timing diagram
POWER/Input
Legend
}
POWER/Input: Supply voltage/input
}
Output safe: Safety contacts
}
Out semi: Semiconductor output
}
t
1
: Switch-on delay
}
t
2
: Delay-on de-energisation
Installation
Install contact expansion module without base unit:
}
Ensure that the plug terminator is inserted at the side of the unit.
Connect base unit and PNOZsigma contact expansion module:
}
Remove the plug terminator at the side of the base unit and at the contact expander
module
}
Connect the base unit and the contact expansion module using the connector supplied,
before mounting the units to the DIN rail.
Control cabinet installation
}
The safety relay should be installed in a control cabinet with a protection type of at least
IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}
When installed vertically: Secure the unit by using a fixing element (e.g. retaining
bracket or end angle).
}
Push the unit upwards or downwards before lifting it from the DIN rail.