Relay outputs
Utilisation category of auxiliary contacts
AC1 at
240 V
Min. current
0,01 A
Max. current
8 A
Max. power
2000 VA
DC1 at
24 V
Min. current
0,01 A
Max. current
8 A
Max. power
200 W
Utilisation category
In accordance with the standard
EN 60947-5-1
Utilisation category of safety contacts
AC15 at
230 V
Max. current
5 A
DC13 (6 cycles/min) at
24 V
Max. current
7 A
Utilisation category of auxiliary contacts
AC15 at
230 V
Max. current
5 A
DC13 (6 cycles/min) at
24 V
Max. current
7 A
Utilisation category in accordance with UL
Voltage
240 V AC G. P.
With current
8 A
Pilot Duty
C300, R300
External contact fuse protection, safety contacts
In accordance with the standard
EN 60947-5-1
Max. melting integral
240 A²s
Blow-out fuse, quick
10 A
Blow-out fuse, slow
6 A
Blow-out fuse, gG
10 A
Circuit breaker 24V AC/DC, characteristic B/C
6 A
External contact fuse protection, auxiliary contacts
Max. melting integral
240 A²s
Blow-out fuse, quick
10 A
Blow-out fuse, slow
6 A
Blow-out fuse, gG
10 A
Circuit breaker 24 V AC/DC, characteristic B/C
6 A
Contact material
0,2 µm Au