PNOZ X13
Operating Manual PNOZ X13
20187-EN-07
| 9
Timing diagram
[1]
[2]
POWER
Start
Input
Output safe
Output aux.
Legend
}
Power: Supply voltage
}
Start: Start circuit
}
Input: Input circuit
}
Output safe: Safety contacts, instantaneous
}
Output aux: Auxiliary contact
}
[1]: Automatic start
}
[2]: Monitored start
}
t
1
: Switch-on delay
}
t
2
: Delay-on de-energisation
}
t
3
: Recovery time
}
t
4
: Waiting period with a monitored start
Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).
}
When installed vertically: Secure the unit by using a fixing element (e.g. retaining bracket
or end angle).
Wiring
Please note:
}
" must be followed.
}
Delivery condition: Link between S11-S12 (dual-channel input circuit)
}
Outputs 13-14, 23-24, 33-34, 43-44, 53-54 are safety contacts; output 61-62 is an auxili-
ary contact (e.g. for display).
}
Auxiliary contact 61-62 should
not
be used for safety circuits!
}
To prevent contact welding, a fuse should be connected before the output contacts (see
}
Calculation of the max. cable length l
max
in the input circuit: