Relay outputs
777600
787600
Utilisation category of safety con-
tacts delayed
AC1 at
240 V
240 V
Min. current
0,01 A
0,01 A
Max. current
6 A
6 A
Max. power
1500 VA
1500 VA
DC1 at
24 V
24 V
Min. current
0,01 A
0,01 A
Max. current
6 A
6 A
Max. power
150 W
150 W
Utilisation category
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Utilisation category of safety con-
tacts delayed
AC15 at
230 V
230 V
Max. current
5 A
5 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
4 A
4 A
Utilisation category in accordance
with UL
Voltage
240 V AC G. P.
240 V AC G. P.
With current
6 A
6 A
Voltage
24 V DC Resistive
24 V DC Resistive
With current
6 A
6 A
Pilot Duty
B300, R300
B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Max. melting integral
100 A²s
100 A²s
Blow-out fuse, quick
6 A
6 A
Blow-out fuse, slow
4 A
4 A
Blow-out fuse, gG
6 A
6 A
Circuit breaker 24V AC/DC,
characteristic B/C
4 A
4 A
Conventional thermal current
6 A
6 A
Contact material
0,2 µm Au
0,2 µm Au
Times
777600
787600
Switch-on delay
With automatic start typ.
100 ms
100 ms
With automatic start max.
210 ms
210 ms
With manual start typ.
35 ms
35 ms
With manual start max.
210 ms
210 ms
Delay-on de-energisation
With power failure typ.
1100 ms
1100 ms
With power failure max.
1500 ms
1500 ms