Connecting the Control System PNOZmulti
Installation Manual PNOZmulti Installation Manual
1002265-EN-02
27
5.9
Motion monitoring modules
Connection technology
}
Proximity switch
Plug-in connection terminals (either cage clamp terminals or screw terminals)
}
Encoder
–
Mini-IO socket with motion monitoring modules PNOZ m EF XMM
–
RJ45 socket with speed monitors PNOZ msXp for configurable safety systems
PNOZmulti
Please note the following when connecting the encoder:
}
The adapter cable should be as short as possible.
}
A shielded connection box should be used for the sensor signals
}
A separate power supply, isolated from the drive, should be used to supply voltage to
the sensors.
INFORMATION
The following applies for the speed monitor PNOZ msXp with RJ45 connec-
tion:
The shield connection for the incremental encoder is established via the
RJ45 connector housing. Use ready-made cable from Pilz (see units' oper-
ating manuals and Technical Catalogue).
INFORMATION
The following applies for motion monitoring modules with Mini-IO connec-
tion:
The shield connection for the encoder is established via the adapter cable
housing on the drive / inverter.
If necessary, the shielding braid on the adapter cable can be connected to
the functional earth via a shield clamp on the mounting rail.
Use ready-made cable from Pilz (see units' operating manuals and Tech-
nical Catalogue).