Safety switches and actuators must be positioned so that they are secured against a
change of position.
}
Attach the safety switches and actuators only with the supplied nuts.
}
Avoid the risk of damages from foreseeable external influences by attaching the safety
switch and actuator. If necessary, safety switch and actuator have to be protected.
INFORMATION
Protect the actuator from unauthorised removal (e.g. via a screw lock or
concealed installation) and from contamination.
}
Prevent self-loosening of the fastening elements of safety switch and actuator.
}
The fastening of safety switch and actuator has to be sufficiently stable to ensure the
proper operation of the safety switch and the actuator.
}
The distance between two safety switches must be maintained (see
).
}
Safety switches and actuators
– Should be kept away from iron swarf
– Should not be exposed to strong magnetic fields
}
Prevent the safety switch and actuator being exposed to heavy shock or vibration.
}
Make sure that the safety switch and actuator cannot be used as an end stop.
}
Circumvention of the safety switch in a reasonably foreseeable manner must be preven-
ted.
}
Please note the installation measures in accordance with EN ISO 14119 for a proximity
switch type 4 with coding level Low.
}
Alignment errors of the guard must not adversely affect the safety function of the guard.
}
The assured operating distance S
ao
and the assured release distance S
ar
must be tested
under real conditions.
}
Do not apply any installation tools (e.g. Pliers) on the surfaces of the switch.
}
If possible, do not install the safety switch and actuator on to ferromagnetic material.
Changes to the operating distances are to be expected.
}
Protect the safety switch and actuator from UV light or direct sunlight.
}
The protection type (see
) can only be achieved by using the
Pilz connection leads available as an accessory.