PSEN ma1.4n-51
Operating Manual PSEN ma1.4n-51
22131-EN-06
| 11
Requirements and connection to evaluation devices
For use of PSEN ma1.4n-51 in accordance with DIN EN 60947-5-3 an evaluation device
must be connected.
Connect the PSEN ma1.4n-51
}
either
with a certified Pilz evaluation device
}
or
with an evaluation device with defined properties
Certified Pilz evaluation devices are, for example:
}
PNOZelog for safety gate monitoring
– PNOZ e1p, PNOZ e1.1p, PNOZ e1vp
– PNOZ e5.11p
– PNOZ e6vp, PNOZ e6.1p
}
PNOZpower for safety gate monitoring
– PNOZ p1p, PNOZ p1vp
}
PNOZsigma for safety gate monitoring
– PNOZ s3
– PNOZ s4
– PNOZ s5
}
PNOZ X for safety gate monitoring
– PNOZ X2, PNOZ X2.5P, PNOZ X2.7P, PNOZ X2.8P, PNOZ X2.9P, PNOZ X2C
– PNOZ X3, PNOZ X3.1, PNOZ X3P, PNOZ X3.10P
– PNOZ X4
– PNOZ X5, PNOZ X5J
– PNOZ Ex
}
PNOZmulti for safety gate monitoring
Configure the switch in the PNOZmulti Configurator with switch type 3.
}
PSS for safety gate monitoring with standard function block SB064, SB066 or
FS_Safety Gate
}
PSSuniversal PLC for safety gate monitoring with function block FS_SafetyGate
The correct connection to the respective evaluation device is described in the operating
manual for the evaluation device. Make sure that the connection is made in accordance
with the specifications in the operating manual for the selected evaluation device.
Defined properties of evaluation devices:
}
2-channel with feasibility monitoring
}
Open circuit monitoring of the safety switch is performed
}
Inputs and outputs on the evaluation device must fulfil the requirements of IEC 61131,
Type 3
}
Technical data of the evaluation device must fulfil the requirements in the
of PSEN ma1.4n-51
– Always comply with the max. switching current safety contacts of PSEN ma1.4n-51.