Project configuration
Operating Manual PSEN op2B/1 Series
1003357-EN-02
34
Icon
Unit
Minimum
value
Maximum value
Description
D
MutingOff
cm
L
Distance between muting
sensor A1 and the position
from which the muting func-
tion is turned off again
Distances for muting with 2 sensors
Muting in two directions with two muting sensors and cross muting
When cross muting is used, please note the following:
}
The intersection point of the muting sensors must be behind the safety light grid, within
the danger zone (see diagram).
}
By arranging the muting sensors asymmetrically you ensure that the muting sensors
must activate consecutively in order to activate a muting state (see diagram).
A1
[1]
B2
V
d2
Fig.: Distances between muting sensors - Cross muting
Legende
[1] Safety light grid
A1 First muting sensor on the input side
B1 Second muting sensor on the input side
Display Unit
Minimum
value
Maximum value
Description
d2
cm
Distance must be
covered within 4 s
Distance that the object covers
from the first muting sensor A1
to the second muting sensor
B2
D
MutingOff
cm
L
Distance between activation of
the muting function and the
position from which the muting
function is switched off again
Distances for cross muting with 2 sensors