Operation
Operating Manual PSEN sc L 3/5 series
1005056-EN-01
| 80
10.5
Restore configuration
Prerequisites
}
The memory module is installed correctly.
}
The pin assignment must be compatible with the data in the memory module.
One of the following conditions must be met.
}
The MIB files in PSEN sc L and in the memory module are different.
}
The topologies in PSEN sc L and in the memory module are different.
}
The serial numbers saved in PSEN sc L and in the memory module are different.
Procedure:
1. Switch the safety laser scanner on.
When the safety laser scanner is already switched on, switch it off and then on again.
The system checks whether the conditions are met. When the conditions are met,
restoring of the configuration is started.
2. Depending on the type of difference between memory module and PSEN sc L the
restoring of the configuration varies.
Serial numbers differ: CFG NO MATCHING is shown on the display. Continue by se-
lecting the data for the restore.
Topology or MIB files vary: WAITING CONF is shown on the display. Continue the con-
figuration in PSENscan Configurator.
3. Use the buttons on the display to select the data to be used for restore.
Display:
Restore cfg
: The configuration in the memory module is used. Confirm the selection
with
Confirm
and the configuration is copied from the memory module into PSEN sc L.
Continue checking the configuration.
cfg from GUI
: The configuration created newly in the PSENscan Configurator is used.
Confirm your selection with
Confirm
and continue with Create new configuration in
PSENscan Configurator.
4. Display:
Confirm
/
Cancel
Confirm your entry with
Confirm
5. Checking the configuration
Display:
RESTORE FAILED. Could not copy the configuration successfully. Continue by select-
ing the data for the restore.
RUN TEST MODE: Select
Enter Test
on the display. Test operation starts. Continue
with accept or reject configuration.
6. Accept or reject configuration
Test operation is complete.
Select
Validate conf
to accept the configuration. The safety laser scanner is ready for
operation again.
Select
Reject conf
to reject the configuration. Continue by selecting the data for the re-
store.