Connecting the Inputs and Outputs
5-10
Installation Manual: PSS 3032
Example: Single-channel, failsafe input device, with test pulse
Features:
• The input device must be approved for failsafe applications.
• Please read the instructions provided with the input device.
• The test pulse must be allocated to the input via the configurator on the
programming device (see Programming Manual).
• Testing will detect short circuits between lines L+ and L-, and also
between the pulsed outputs.
• Short circuits between the cable from the signal to the input device and
the cable from the input device to the input will not be detected.
• Only input devices with N/C contacts can be tested.